In order to study the operational characteristics of a combined solar photovoltaic-thermal system and multi-source heating system
an experimental platform for a solar photovoltaic-thermal combined dual-source heat pump system was constructed. The system was tested in heating
cooling
and hot water production modes
with a focus on analyzing the heat output
COP
electricity consumption
etc.
when heating from the PV/T source and air source in heating hot water production and heating modes. The impact of heating from the PV/T water tank on the electrical and thermal efficiency of the PV/T panel was also examined
along with an analysis of the system's energy saving performance during actual operation. The experimental results indicate that in heating mode during cold and sunny winter weather
the average COP of the heat pump unit is 2.18
while the system's average COP is 3.17
with heating from the PV/T source accounting for 61.57% of the operating time. In the hot water production mode
at the same heating temperature
the heat pump performance is superior when heating from the PV/T source compared to heating from the air source. Heating from the PV/T water tank can effectively reduce the temperature of the PV/T panel
thereby enhancing its electrical and thermal efficiency.
KASAEIAN A, BELLOS E, SHAMAEIZADEH A, et al.Solar-driven polygeneration systems: recent progress and outlook[J]. Applied energy, 2020, 264: 114764.
WU J H, XIAN T, LIU X.All-weather characteristic studies of a direct expansion solar integrated air source heat pump system based on PCMs[J]. Solar energy, 2019, 191: 34-45.
HANDS S, SETHUVENKATRAMAN S, PERISTY M, et al.Performance analysis & energy benefits of a desiccant based solar assisted trigeneration system in a building[J].Renewable energy, 2016, 85: 865-879.
SHAO N N, MA L D, ZHANG J L.Experimental investigation on the performance of direct-expansion roof-PV/T heat pump system[J]. Energy, 2020, 195: 116959.