LYU Jianshuang, BAI Xiaolu, ZHANG Hu, et al. Dynamic tension characteristics of non-uniform ice-shedding on transmission lines in moderate ice zones[J]. Ningxia Electric Power, 2023, (6).
LYU Jianshuang, BAI Xiaolu, ZHANG Hu, et al. Dynamic tension characteristics of non-uniform ice-shedding on transmission lines in moderate ice zones[J]. Ningxia Electric Power, 2023, (6).DOI: 10.3969/j.issn.1672-3643.2023.06.008.
Non-uniform ice-shedding on transmission lines is a significant contributor to line faults and defects.To analyze the dynamic tension variations during the ice-shedding process in moderate ice zones
a finite element model
representing the continuous span-tower coupled system under typical design conditions
is established using finite element analysis software.This study examines the influence of various voltage levels and factors on the dynamic tension characteristics of ice-shedding and derives a fitting calculation formula.Results show that factors such as ice-shedding rate
icing thickness
span length
and conductor type have a significant impact on the tension disparities of the conductor.In contrast
the number of spans and height differences have minimal impacts.For overhead transmission lines in moderate ice regions
the peak unbalanced tension difference in the conductor after ice-shedding is about 1.71 times that of the steady-state unbalanced tension.It is crucial in design considerations to acknowledge the potential destructive impact of the instantaneous peak on the tower-line system.