Ye Li, Na Jia, Jiawei He, 等. Non-unit protection scheme based on cooperation with control strategy for multiterminal hybrid HVDC system without line boundary[J]. 现代电力系统保护与控制(英文), 2025,10(5).
Ye Li, Na Jia, Jiawei He, et al. Non-unit protection scheme based on cooperation with control strategy for multiterminal hybrid HVDC system without line boundary[J]. Protection and Control of Modern Power Systems, 2025, 10(5).
Ye Li, Na Jia, Jiawei He, 等. Non-unit protection scheme based on cooperation with control strategy for multiterminal hybrid HVDC system without line boundary[J]. 现代电力系统保护与控制(英文), 2025,10(5).DOI: 10.23919/PCMP.2024.000190.
Ye Li, Na Jia, Jiawei He, et al. Non-unit protection scheme based on cooperation with control strategy for multiterminal hybrid HVDC system without line boundary[J]. Protection and Control of Modern Power Systems, 2025, 10(5).DOI: 10.23919/PCMP.2024.000190.
Non-unit protection scheme based on cooperation with control strategy for multiterminal hybrid HVDC system without line boundary
摘要
Abstract
Multiterminal hybrid HVDC systems
combining the advantages of conventional and flexible DC systems
are considered important development trends for future power networks. With the ability to suppress DC fault current
hybrid HVDC systems eliminate the requirement of current limiting reactors at both ends of DC lines. Thus
non-unit protection based on line boundaries is no longer applicable. In this paper
a non-unit protection scheme in cooperation with converter control is proposed to ensure protection speed
reliability
and sensitivity for multiterminal hybrid HVDC systems without line boundaries. In the proposed protection scheme
the protection criterion based on the transient energy of the DC voltage and the direction criterion based on the travelling wave are used to identify whether the fault occurs on the DC line. When the fault is detected as a DC-line fault
the relevant converter station is quickly blocked. After a specified hold-off duration
the converter station interfacing with multiple DC lines is prioritized for restart
while the remaining converter stations are restarted once the DC voltage is stabilized. Simulations based on PSCAD/EMTDC validate the feasibility of the proposed protection scheme and its superiority over competing approaches.
Reliability-Based Design Optimization for Lithium-ion Batteries Considering the Venting Critical Time
Intelligent Self-Adjusting Protection Algorithm for Smart LVDC Distribution Networks
Dual Alternative Iteration Algorithm-Based Hierarchical MPC Strategy for Frequency Regulation Control and Active Power Allocation of Wind-storage Coupling System
Application of Improved Crown Porcupine Optimizer in UAV Path Planning Based on Dynamic Weighted JAYA-CPO Attack Strategy
An Optimized Distribution Model for Energy System in Virtual Power Plants Integrating Electric Vehicles Based on TD3 and DQN