陈瑞, 郑少明, 刘博, 等. 雷击条件下柔性直流输电同杆并架线路相互影响仿真分析[J]. 山东电力技术, 2025,52(7):35-43.
陈瑞, 郑少明, 刘博, 等. 雷击条件下柔性直流输电同杆并架线路相互影响仿真分析[J]. 山东电力技术, 2025,52(7):35-43. DOI: 10.20097/j.cnki.issn1007-9904.2025.07.004.
分析同杆并架线路之间的相互影响及雷电行波遇到同杆并架线路时的传播特点,并仿真了张北柔性直流输电工程阜延线路正极遭遇雷击的情况。通过仿真与实际波形的对比,分析了阜延线路正极及中延线路正极各侧的电压、电流波形特征及雷电波传播特征。结果表明,当雷电流击打到阜延线路后,雷电波向阜延线路两侧传播,因电磁耦合作用在中延线路上产生感应雷电波,并向两侧传播;同杆并架线路分界点两侧入射至分界点的不同模量行波会在分界点发生交叉折射,因此会造成中延线路两侧感应雷电波的不同;之后雷电波与感应雷电波在换流站侧均发生折射和反射。以上因素共同作用会造成同杆并架正常运行的线路电压和电流发生扰动,进而会造成行波保护动作。本研究对直流输电同杆并架线路在面对雷击时的预防和直流线路行波保护装置保护逻辑的设定有参考意义。
In this paper
the interaction between the lines on the same tower and the propagation characteristics of lightning traveling waves when they encounter the lines on the same tower are analyzed
and the lightning strike on the positive pole of Fuyan line of Zhangbei Flexible HVDC Transmission Project is simulated. By comparing the simulation with the actual waveform
the characteristics of the positive electrode voltage and current waveform on each side of Fuyan line and Zhongyan line and the characteristics of lightning wave propagation are analyzed.The results showed that when the lightning current hit the Fuyan line
the lightning wave propagates to both sides of the Fuyan line
and induced lightning wave is generated on the Zhongyan line due to electromagnetic coupling
which propagates to both sides of the Fuyan line. Moreover
the travelling waves of different modulus incident on both sides of the line demarcation point will cross refract at the demarcation point
which causes the difference of induced lightning waves in two sides of the Zhongyan line.After that
both the lightning wave and the induced lightning wave are refracted and reflected at the converter station.The combined action of the above factors will cause the disturbance of the line voltage and current in the normal operation on the same tower
and can cause traveling wave protection action.This research have reference significance for the prevention measures when facing lightning strike on DC lines on the same tower and the setting of the relay protection logic of the DC line traveling wave relay protection device.