To address the limitations of adopting single conductor erection mode in research on the electromagnetic environmental impacts of 750 kV transmission lines
four typical erection schemes are selected: single-circuit lines
double- circuit lines on the same tower
parallel single-circuit lines
and parallel layout of single-circuit lines and double-circuit lines on the same tower. On the basis of electromagnetic induction theory and superposition principle
the equivalent charge method and Ampère′s law are used to predict electromagnetic impacts and conduct compliance analysis. By clarifying key parameters including tower types
conductor parameters and conductor height above ground for each scenario
the distribution of electromagnetic field strength at 1.5 m above the ground is predicted. Compliance evaluation is carried out in accordance with GB 8702—2014“Controlling Limits for Electromagnetic Environment”. The results show that affected by conductor height
phase spacing and erection mode
the maximum electromagnetic field strength of the four schemes is located in the center or near the line corridor. By differentially increasing the conductor heights
the power frequency electric field strength can meet the control limit of 10 kV/m applicable to non-residential areas
and the power frequency magnetic flux density ranges from 12.39 μT to 28.19 μT