徐敏, 杨洪, 黄嘉盛, 等. 基于低频高压阻抗测量的10 kV XLPE电缆绝缘早期老化评估研究[J]. 内蒙古电力技术, 2026,(4).
徐敏, 杨洪, 黄嘉盛, et al. 基于低频高压阻抗测量的10 kV XLPE电缆绝缘早期老化评估研究[J]. 2026, (4).
徐敏, 杨洪, 黄嘉盛, 等. 基于低频高压阻抗测量的10 kV XLPE电缆绝缘早期老化评估研究[J]. 内蒙古电力技术, 2026,(4). DOI: 10.19929/j.cnki.nmgdljs.2026.0045.
徐敏, 杨洪, 黄嘉盛, et al. 基于低频高压阻抗测量的10 kV XLPE电缆绝缘早期老化评估研究[J]. 2026, (4). DOI: 10.19929/j.cnki.nmgdljs.2026.0045.
10 kV交联聚乙烯(cross-linked polyethylene,XLPE)电缆是城市配电网的重要组成部分,其绝缘性能直接影响供电可靠性。本文基于电压-电流比值法,设计了一种适用于10 kV电缆额定相电压工况、0.1~100 Hz频率范围内的低频高压阻抗测试电路。回路中串联一支阻值与电缆容抗同数量级的保护电阻,用于放大轻微绝缘劣化引起的电容和绝缘电阻微小变化;同时,结合XLPE绝缘片状试样的微观检测,实现对电缆绝缘状态的综合评估。结果表明,对0.5 mm厚XLPE绝缘片状试样的傅里叶变换红外光谱和差示扫描量热分析,各老化阶段材料均处于轻微劣化状态。电缆电容在不同温度下均随老化时间增加而减小;绝缘电阻在30℃基本保持不变,在90℃时呈单调下降趋势。仿真计算与模拟实验结果显示,串联保护电阻后端口电压与电流之间产生显著相位差,且相位角和阻抗幅值均随频率升高而减小。在6 kV下得到的等效电容明显高于传统LCR测试仪在低压下的测量值,但二者在0.1~100 Hz范围内电容量变化均较小,仅在0.1 Hz时由于极化效应增强导致电容量显著增加。综合宏观高压阻抗测试与微观表征结果可知,基于电压-电流比值法的低频高压阻抗测试方法与传统阻抗测试及微观检测试验结果具有良好的一致性,且在低频段对轻微劣化电缆绝缘具有更高的检测灵敏度。
10 kV cross-linked polyethylene(XLPE) cables are an essential part of urban distribution networks
and the reliability of power supply is directly affected by their insulation performance. Based on the voltage current ration method
this paper designs a low-frequency high-voltage impedance testing circuit suitable for the rated phase voltage of 10 kV cables and the frequency range from 0.1 Hz to 100 Hz. A protective resistor with a resistance of the same order as the cable capacitive reactance is connected in series to magnify small changes of capacitance and insulation resistance caused by slight insulation degradation. At the same time
by combining the microscopic inspection of XLPE insulation slices
a comprehensive assessment of cable insulation condition is achieved. The results show that the Fourier transform infrared spectroscopy and differential scanning calorimetry analysis of the 0.5 mm thick XLPE insulation slice samples indicates that the materials are in a slightly deteriorated state at each aging stage. The cable capacitance decreases with the increasing aging time at different temperatures. The insulation resistance remained nearly unchanged at 30 ℃ and decreases monotonically at 90 ℃. The simulation calculation and experimental results indicates that
after the series protective resistor is inserted
there is a significant phase difference between terminal voltage and current
and both the phase angle and the impedance amplitude decrease as the frequency increased. The equivalent capacitance obtained at 6 kV is significantly higher than the value measured at low voltage by a traditional LCR meter. However
in both cases the capacitance change little from 0.1 Hz to 100 Hz and increases notably at 0.1 Hz due to enhanced polarization. By integrating the macroscopic high-voltage impedance tests with microscopic characterization
the low-frequency high-voltage impedance testing method based on the voltage-current ratio method has good consistency with conventional impedance testing and microscopic detection test results and provided higher detection sensitivity for slightly degraded insulation in cables at low frequencies.