During a power outage test on a 220 kV transformer
it is found that the data and waveform of the test items such as dielectric loss
capacitance and short-circuit impedance are abnormal. Through the comprehensive diagnosis and analysis of oil chromatography test
dielectric loss and capacitance test
short-circuit impedance test and so on
it is preliminarily determined that there may be deformation in the windings of the medium voltage side and low voltage side of the transformer. After returning to the factory for inspection
the correctness of the theoretical analysis is verified. It is suggested that routine tests and other routine operation and maintenance of transformers should be carried out regularly.