In order to study the aging performance of composite insulators under the condition of significant temperature difference and intense ultraviolet radiation in the desert-gobi-wasteland area of Inner Mongolia power grid
thereby improving the operational maintenance standards of composite insulators
aging tests involving cold and hot aging
UV aging
and a combination of both are conducted on high-temperature vulcanized silicone rubber samples. It is revealed that UV aging test results in the greatest reduction of static contact angle of the samples
and the aging degree of ultraviolet aging on composite insulators is stronger than that of cold and hot aging
which can weaken or break some Si-C bonds and reduce the surface hydrophobicity
while the aging degree of first cold and hot aging and then ultraviolet aging on composite insulators is between the other two. There is an interaction between the two aging methods
leading to partial breakage of C-H bonds within the CH3 groups of the material
thus affecting the overall performance. Relevant conclusions provide reference for the aging research of composite insulators and the application of such materials in transmission lines.