电网防灾减灾全国重点实验室(长沙理工大学),湖南,长沙,410114
纸质出版:2026
移动端阅览
周泽华, 曾祥君, 喻 锟, 等. 基于格兰杰因果关系的故障行波波头标定新方法[J]. 电力系统保护与控制, 2026,54(20).
ZHOU Zehua, ZENG Xiangjun, YU Kun, et al. A novel method for fault traveling wave head calibration based on Granger causality[J]. Power System Protection and Control, 2026, 54(20).
周泽华, 曾祥君, 喻 锟, 等. 基于格兰杰因果关系的故障行波波头标定新方法[J]. 电力系统保护与控制, 2026,54(20). DOI: 10.19783/j.cnki.pspc.260416.
ZHOU Zehua, ZENG Xiangjun, YU Kun, et al. A novel method for fault traveling wave head calibration based on Granger causality[J]. Power System Protection and Control, 2026, 54(20). DOI: 10.19783/j.cnki.pspc.260416.
针对现有行波波头标定方法易受噪声与波头畸变影响,而基于深度学习的改进方案又存在可解释性不足的问题,提出一种基于格兰杰因果关系的故障行波波头标定方法。首先,分析故障行波传播特性,建立检测端行波信号数学模型,揭示切片后各信号片段之间由折反射与传输过程决定的因果关联。随后,将相邻子样本构建为潜在因果对,利用格兰杰因果关系法计算每对相邻子样本之间的因果强度,并分别构建特征矩阵与邻接矩阵。最后,建立图神经网络-长短期记忆神经(graph neural network and long short-term memory
GNN-LSTM)网络模型,实现故障行波波头到达时刻的精确标定。试验结果表明,所提方法在混合线路及多分支线路中均具有良好的适应性,且受过渡电阻、噪声、故障初相角及故障类型变化影响较小,在配电网拓扑变化情况下仍能保持较高的检测精度,具有较好的工程应用前景。
To address the susceptibility of existing traveling-wave head identification methods to noise and wavefront distortion
as well as the lack of interpretability in improved approaches based on deep learning
a fault traveling-wave head identification method based on Granger causality is proposed. First
the propagation characteristics of fault traveling waves are analyzed
and a mathematical model of the traveling-wave signal at the detection terminal is established to reveal the causal relationships among sliced signal segments
which are determined by the reflection
refraction
and transmission processes. Subsequently
adjacent sub-samples are constructed as potential causal pairs
and the Granger causality method is employed to calculate the causal strength between each pair of adjacent sub-samples. Feature and adjacency matrices are then constructed accordingly. Finally
a graph neural network and long short-term memory (GNN-LSTM) network model is developed to accurately identify the arrival time of the fault traveling-wave head. Experimental results demonstrate that the proposed method exhibits good adaptability to both hybrid and multi-branch lines and is less affected by variations in transition resistance
noise
fault inception angle
and fault type. It also maintains high detection accuracy under changes in distribution network topology
demonstrating good engineering application prospects.
LIU K, ZHANG S, LI B, et al. Flexible grounding system for single-phase to ground faults in distribution networks: a systematic review of developments[J]. IEEE Transactions on Power Delivery, 2021, 37(3): 1640-1649.
WANG Dong, YU Dachuan, GAO Houlei, et al. Frequency modification algorithm-based traveling wave fault location approach for overhead transmission lines with structural changes[J]. Protection and Control of Modern Power Systems, 2025, 10(2): 1-12.
XIE L, LUO L, LI Y, et al. A traveling wave-based fault location method employing VMD-TEO for distribution network[J]. IEEE Transactions on Power Delivery, 2019, 35(4): 1987-1998.
LAN S, CHEN M, CHEN D. A novel HVDC double- terminal non-synchronous fault location method based on convolutional neural network[J]. IEEE Transactions on Power Delivery, 2019, 12(2): 801-809.
XIA Y, LI Z, XI Y, et al. Distribution network fault location method based on wide scale time window difference operator[J]. IEEE Transactions on Industrial Informatics, 2024, 20(3): 3446-3455.
JIA K, YANG B, BI T, et al. An improved sparse- measurement-based fault location technology for distribution networks[J]. IEEE Transactions on Industrial Informatics, 2020, 17(3): 1712-1720.
0
浏览量
0
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621