纸质出版:2026
移动端阅览
董 红, 程培军, 胡柳君, 等. 计及SOC自适应调制的风储联合系统多阶段动态调频策略[J]. 电力系统保护与控制, 2026,54(19).
DONG Hong, CHENG Peijun, HU Liujun, et al. Multi-stage dynamic frequency regulation strategy for wind-storage integrated systems considering adaptive SOC modulation[J]. Power System Protection and Control, 2026, 54(19).
董 红, 程培军, 胡柳君, 等. 计及SOC自适应调制的风储联合系统多阶段动态调频策略[J]. 电力系统保护与控制, 2026,54(19). DOI: 10.19783/j.cnki.pspc.260291.
DONG Hong, CHENG Peijun, HU Liujun, et al. Multi-stage dynamic frequency regulation strategy for wind-storage integrated systems considering adaptive SOC modulation[J]. Power System Protection and Control, 2026, 54(19). DOI: 10.19783/j.cnki.pspc.260291.
针对高渗透率风电系统中传统储能调频策略难以适应多调频阶段差异化需求,且易因储能荷电状态(state of charge
SOC)越限引发频率二次跌落的问题,提出一种计及SOC自适应调制的风储联合系统多阶段动态调频策略。首先,分析了系统等效频率响应特性,明确了不同调频阶段的控制需求差异。其次,构建了双向非对称Sigmoid型自适应调制函数,实现了风储联合调频控制参数在不同调频阶段间的平滑切换与自适应匹配。最后,搭建时域仿真模型开展多工况对比验证。结果表明,与传统调频方案相比,所提策略可将系统最大频率变化率由0.58 Hz/s降低至0.51 Hz/s。在储能初始SOC为0.3的低电量工况下,可使系统频率最低点提升0.03 Hz,并使储能SOC始终维持在15%的安全阈值以上,有效降低频率二次跌落风险,提升系统频率安全边界与储能长期调频运行能力。
To address the problem that traditional energy storage frequency regulation strategies struggle to adapt to the differentiated requirements across multiple frequency regulation stages in high-penetration wind power systems
as well as the risk of secondary frequency drops due to state-of-charge (SOC) violations
a multi-stage dynamic frequency regulation strategy for wind-storage integrated systems considering SOC-adaptive modulation is proposed. First
the equivalent frequency response characteristics of the system are analyzed
and the differences in control requirements among different frequency regulation stages are clarified. Second
a bidirectional asymmetric Sigmoid-type adaptive modulation function is constructed to achieve smooth switching and adaptive matching of control parameters for the wind-storage coordinated frequency regulation across different stages. Finally
a time-domain simulation model is built for multi-condition comparative verification. The results show that
compared with conventional frequency regulation schemes
the proposed strategy reduces the maximum rate of change of frequency from 0.58 Hz/s to 0.51 Hz/s. Under a low-SOC condition with an initial SOC of 0.3
it improves the frequency nadir by 0.03 Hz while maintaining the SOC above the 15% safety threshold throughout the process. This effectively reduces the risk of secondary frequency drop and improves both the system frequency security margin and the long-term frequency regulation capability of the energy storage system.
HAN Yufei, ZHOU Yibo, LI Kexin. A two-stage coordinated frequency regulation strategy for wind turbines considering secondary frequency drop and rotor speed recovery[J]. Energies, 2026, 19(2).
LI Zhijie, DAI Pengfei, LIU Haoyu. Frequency regulation parameters optimization for double-fed wind power grid- connected system based on perturbation theory[J]. Electric Power Systems Research, 2026, 256.
XIE Zhenjian, TANG Yi. Evaluating the minimum inertia of power systems with consideration for wind power in frequency regulation[J]. International Journal of Electrical Power Energy Systems, 2026, 175.
CAI Zhenhua, LIU Xubin, LI Canbing, et al. Dual alternative iteration algorithm-based hierarchical MPC strategy for frequency regulation control and active power allocation of wind-storage coupling system[J]. Protection and Control of Modern Power Systems, 2025, 10(6): 160-175.
HE Yutong, RUAN Guangchun, ZHONG Haiwang. Performance-aware control of modular batteries for fast frequency response[J]. IEEE Transactions on Sustainable Energy, 2025, 16(4): 2547-2559.
NEBULONI R, ILEA V, BERIZZI A, et al. A MILP battery degradation logarithmic model with real-time cycle counting calculation[J]. IEEE Transactions on Industry Applications, 2025, 61(6): 8297-8306.
0
浏览量
0
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621