纸质出版:2026
移动端阅览
陈智勇, 古江, 罗文华, 等. 一种基于边界频率的并网逆变器无源性优化方法[J]. 电力系统保护与控制, 2026,54(12).
CHEN Zhiyong, GU Jiang, LUO Wenhua, et al. A boundary-frequency-based passivity optimization method for grid-connected inverters[J]. Power System Protection and Control, 2026, 54(12).
陈智勇, 古江, 罗文华, 等. 一种基于边界频率的并网逆变器无源性优化方法[J]. 电力系统保护与控制, 2026,54(12). DOI: 10.19783/j.cnki.pspc.251017.
CHEN Zhiyong, GU Jiang, LUO Wenhua, et al. A boundary-frequency-based passivity optimization method for grid-connected inverters[J]. Power System Protection and Control, 2026, 54(12). DOI: 10.19783/j.cnki.pspc.251017.
目前,针对比例谐振 (proportional-resonant
PR) 控制器引入的相位滞后对并网逆变器输出导纳无源性的影响尚缺乏系统性研究,且已有相位补偿方法多依赖试凑,缺乏解析设计依据。为此,提出一种基于边界频率的无源性优化方法。首先,建立计及控制器相位滞后的逆变器输出导纳模型,归纳出两类无源区边界频率。基于两类边界频率间的相对关系,设计一种与 PR 控制器级联的一阶相位补偿器,将无源区拓展至奈奎斯特频率。在不增加传感器的条件下,进一步引入公共连接点 (point of common coupling
PCC) 电压前馈环节,增强边界频率处的无源鲁棒性。最后,基于一台 4.8 kW 逆变器样机开展实验验证,结果表明,所提方法在感性 / 容性弱电网条件及滤波器参数波动下,均能有效维持系统稳定运行。
At present
there is a lack of systematic research on the impact of phase lag introduced by proportional-resonant (PR) controllers on the passivity of the output admittance of grid-connected inverters. Moreover
existing phase compensation methods are largely based on trial-and-error tuning and lack analytical design criteria. To address these issues
this paper proposes a boundary-frequency-based passivity optimization method. First
an inverter output admittance model that accounts for the phase-lag effect of the PR controller is established
and two types of boundary frequencies defining the passive region are identified. Based on the relative position of the two boundary frequencies
a first-order phase compensator cascaded with the PR controller is designed to extend the passivity region up to the Nyquist frequency. Furthermore
without requiring additional sensors
a point-of-common-coupling (PCC) voltage feedforward is introduced to enhance passivity robustness at the boundary frequencies. Finally
experiments on a 4.8 kW inverter prototype confirm that the proposed approach maintains stable operation under inductive/capacitive weak-grid conditions
as well as in the presence of filter parameter variations.
BLAABJERG F, CHEN Z, KJAER S B. Power electronics as efficient interface in dispersed power generation systems[J]. IEEE Transactions on Power Electronics, 2004, 19(5): 1184-1194.
XU H, YU C, CHEN C, et al. Impedance model-based stability analysis of single-stage grid-connected inverters considering PV panel characteristics and DC-side voltage[J]. Protection and Control of Modern Power Systems, 2025, 10(4): 130-145.
TANG Y, LOH P C, WANG P, et al. Generalized design of high performance shunt active power filter with output LCL filter[J]. IEEE Transactions on Industrial Electronics, 2012, 59(3): 1443-1452.
TANG W, MA K, SONG Y. Critical damping ratio to ensure design efficiency and stability of LCL filters[J]. IEEE Transactions on Power Electronics, 2021, 36(1): 315-325.
PARKER S G, MCGRATH B P, HOLMES D G. Regions of active damping control for LCL filters[J]. IEEE Transactions on Industry Applications, 2014, 50(1): 424-432.
PAN D, RUAN X, BAO C, et al. Capacitor current feedback active damping with reduced computation delay for improving robustness of LCL-type grid-connected inverter[J]. IEEE Transactions on Power Electronics, 2014, 29(7): 3414-3427.
FANG T, SHEN S, ZHANG L, et al. Capacitor current feedback with phase-lead compensator to eliminate resonant frequency forbidden region for LCL-type grid-connected inverter in weak grid [J]. IEEE Journal of Emerging and Selected Topics in Power Electronics, 2021, 9(5): 5581-5596.
LI S, LIN H. A capacitor-current-feedback positive active damping control strategy for LCL-type grid-connected inverter to achieve high robustness[J]. IEEE Transactions on Power Electronics, 2022, 37(6): 6462-6474.
ZHANG H, WANG X, HE Y, et al. A compensation method to eliminate the impact of time delay on capacitor-current active damping[J]. IEEE Transactions on Industrial Electronics, 2022, 69(7): 7512-7516.
UPADHYAY N, PADHY N P, AGARWAL P. Grid-current control with inverter-current feedback active damping for LCL grid-connected inverter[J]. IEEE Transactions on Industry Applications, 2024, 60(1): 1738-1749.
PAN D, RUAN X, WANG X. Direct realization of digital differentiators in discrete domain for active damping of LCL-type grid-connected inverter[J]. IEEE Transactions on Power Electronics, 2018, 33(10): 8461-8473.
ZHANG H, RUAN X, LIN Z, et al. Capacitor voltage full feedback scheme for LCL-type grid-connected inverter to suppress current distortion due to grid voltage harmonics[J]. IEEE Transactions on Power Electronics, 2021, 36(3): 2996-3006.
LI W, RUAN X, PAN D, et al. Full-feedforward schemes of grid voltages for a three-phase LCL-type grid-connected inverter[J]. IEEE Transactions on Industrial Electronics, 2013, 60(6): 2237-2250.
LI X, FANG J, TANG Y, et al. Robust design of LCL filters for single-current-loop-controlled grid-connected power converters with unit PCC voltage feedforward[J]. IEEE Journal of Emerging and Selected Topics in Power Electronics, 2018, 6(1): 54-72.
YE J, WANG H, LI B, et al. Passivity-based controller design of PCC voltage feedforward active damping for grid-connected inverters[J]. IEEE Transactions on Industrial Electronics, 2024, 71(8): 8752-8762.
HE S, ZHOU D, WANG X, et al. Passivity-based multisampled converter-side current control of LCL-filtered VSCs[J]. IEEE Transactions on Power Electronics, 2022, 37(11): 13848-13860.
HE S, YANG Z, ZHOU D, et al. Dissipativity robustness enhancement for LCL-filtered grid-connected VSCs with multisampled grid-side current control[J]. IEEE Transactions on Power Electronics, 2023, 38(3): 3992-4004.
ZHAO J, XIE C, LI K, et al. Passivity-oriented design of LCL-type grid-connected inverters with Luenberger observer-based active damping[J]. IEEE Transactions on Power Electronics, 2022, 37(3): 2625-2635.
AKHAVAN A, VASQUEZ J C, GUERRERO J M. A simple method for passivity enhancement of current controlled grid-connected inverters[J]. IEEE Transactions on Power Electronics, 2020, 35(8): 7735-7741.
LI C, XIE C, MA G, et al. Passivity and injection current quality enhancement for single inverter-side current feedback LCL-type grid-following inverters[J]. IEEE Journal of Emerging and Selected Topics in Power Electronics, 2025, 13(2): 2500-2511.
WANG X, HE Y, PAN D, et al. Passivity enhancement for LCL-filtered inverter with grid current control and capacitor current active damping[J]. IEEE Transactions on Power Electronics, 2022, 37(4): 3801-3812.
LI S, LIN H. Passivity enhancement-based general design of capacitor current active damping for LCL-type grid-tied inverter[J]. IEEE Transactions on Power Electronics, 2023, 38(7): 8223-8236.
HUANG Y, XIE C, PENG C, et al. Rethink and design of capacitor-current-feedback active damping for grid-following inverters from a passivity enhancement perspective[J]. IEEE Journal of Emerging and Selected Topics in Power Electronics, 2024, 12(3): 2947-2959.
HARNEFORS L, YEPES A G, VIDAL A, et al. Passivity-based controller design of grid-connected VSCs for prevention of electrical resonance instability[J]. IEEE Transactions on Industrial Electronics, 2015, 62(2): 702-710.
CHEN Z, LI B, WANG B. Robust stability design for inverters using phase lag in proportional-resonant controllers[J]. IEEE Transactions on Industrial Electronics, 2025, 72(3): 2655-2668.
0
浏览量
0
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621