苏森杨, 李滨涛, 郑宗华, et al. 基于混合式限流装置提升ISOP-DAB直流系统暂态性能关键技术研究[J]. Power System Protection and Control, 2026, (4). DOI: 10.19783/j.cnki.pspc.250482.
基于混合式限流装置提升ISOP-DAB直流系统暂态性能关键技术研究
摘要
为解决双有源桥短路工况下线路阻抗低、电流峰值大、恢复时间长等问题,提出了一种基于耦合电感与高频斩波回路融合的混合式新型限流装置。首先,推导计及新型限流装置的直流系统故障暂态数学模型及限流原理,分析了电阻、电感、变压器变比等关键参数对限流效果的影响。其次,结合电压微分判据实现故障快速检测,并通过对双有源桥出口电压的连续检测,实现永久/瞬时性故障类型的判别,配合直流断路器精准开断。最后,在输入串联输出并联-双有源桥(input series output parallel-dual active bridge
and long recovery time under short-circuit conditions in dual active bridge (DAB) converters
this paper proposes a novel hybrid current-limiting device integrating coupled inductors a high-frequency chopper circuit. First
a transient mathematical model of the DC system incorporating the proposed current-limiting device is derived
and the current-limiting principle is explained. The impacts of critical parameters such as resistance
inductance
and transformer turns ratio on the current-limiting performance are systematically analyzed. Subsequently
a voltage derivative criterion is developed for rapid fault detection
while permanent/transient fault discrimination is achieved through continuous monitoring of the DAB output voltage
enabling coordinated operation with DC circuit breakers for precise interruption. Finally
comprehensive simulations are conducted on an input series output parallel-dual active bridge (ISOP-DAB) DC system under transient and permanent faults as well as pole-to-pole/pole-to-ground short-circuit faults. The simulation results demonstrate that
compared with conventional current limiters
the proposed solution reduces the short-circuit current peak by over 85% and shortens the fault isolation time by more than 40%
exhibiting superior performance in fault current suppression and system recovery acceleration.