1. 1.上海电力大学电气工程学院,上海,200090
2. 国网技术学院,山东,济南,250002
3. 国网上海市电力公司,上海,200437
纸质出版:2025
移动端阅览
邓祥力, 刘美含, 曾平, 等. 基于漏磁场相位变化特征的变压器绕组早期故障保护研究[J]. 电力系统保护与控制, 2025,(24).
DENG Xiangli, LIU Meihan, ZENG Ping, et al. 基于漏磁场相位变化特征的变压器绕组早期故障保护研究[J]. Power System Protection and Control, 2025, (24).
邓祥力, 刘美含, 曾平, 等. 基于漏磁场相位变化特征的变压器绕组早期故障保护研究[J]. 电力系统保护与控制, 2025,(24). DOI: 10.19783/j.cnki.pspc.250109.
DENG Xiangli, LIU Meihan, ZENG Ping, et al. 基于漏磁场相位变化特征的变压器绕组早期故障保护研究[J]. Power System Protection and Control, 2025, (24). DOI: 10.19783/j.cnki.pspc.250109.
针对传统变压器保护难以有效识别变压器绕组轻微匝间短路类早期故障的问题,提出一种基于漏磁场相位变化特征的变压器绕组早期故障保护方案。首先,建立非理想绕组结构变压器漏磁场解析模型,计算分析绕组故障前后漏磁分布变化规律。然后,结合漏磁相位突变量、不同测点漏磁相位差等故障分量及漏磁幅值比信息,提出漏磁相位差动保护判据和故障定位逻辑,避免了温度对光纤测量系统的影响。并利用漏磁场解析模型进行保护动作定值整定。最后,通过动模实验与有限元仿真模型验证了所提早期故障判别与定位方案的可行性和有效性。
To address the difficulty of traditional transformer protection in effectively identifying early-stage faults such as minor inter-turn short circuits in transformer windings
this paper proposes an early fault protection scheme for transformer windings based on the phase change characteristics of the leakage magnetic field. First
an analytical model of the leakage magnetic field for a transformer with a non-ideal winding structure is established
and the variation of magnetic leakage distribution before and after winding failures is analyzed. Then
by combining the fault components such as magnetic leakage phase mutation
phase differences among multiple measuring points
and leakage amplitude ratio
a leakage phase differential protection criterion and a fault location logic are proposed
effectively avoiding the influence of temperature on the optical fiber measurement system. The leakage magnetic field analytical model is also used for setting the operating thresholds of the protection scheme. Finally
the feasibility and effectiveness of the proposed early fault identification and location scheme are verified by dynamic model experiments and finite element simulations.
0
浏览量
50
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621