纸质出版:2025
移动端阅览
高波. 基于PSO-ELM的可植入UPQC的“源-网-荷-储”系统最优控制策略[J]. 电力系统保护与控制, 2025,45(2).
GAO Bo. 基于PSO-ELM的可植入UPQC的“源-网-荷-储”系统最优控制策略[J]. Power System Protection and Control, 2025, 45(2).
高波. 基于PSO-ELM的可植入UPQC的“源-网-荷-储”系统最优控制策略[J]. 电力系统保护与控制, 2025,45(2). DOI: 10.19783/j.cnki.pspc.240749.
GAO Bo. 基于PSO-ELM的可植入UPQC的“源-网-荷-储”系统最优控制策略[J]. Power System Protection and Control, 2025, 45(2). DOI: 10.19783/j.cnki.pspc.240749.
针对传统“源-网-荷-储”(source network load storage
SNLS)系统的可再生能源渗透率低及电能质量差等问题,提出了一种可植入统一电能质量调节器(unified power quality conditioner
UPQC)的SNLS系统最优控制方案。该方案通过基于粒子群优化(particle swarm optimization
PSO)的极限学习机(extreme learning machine
ELM)方法实现。在多目标优化运行方案中:第一个优化目标为最大化光伏阵列发电量;第二、三个优化目标分别为最小化负荷电压偏差和最大化网侧功率因数;第四个优化目标则为最大化变换器的利用率。由于多目标优化问题不易实时求解,提出了一种基于优化目标优先权顺序的分层优化思想,将多目标优化问题简化为若干个单目标优化问题。然后,通过将求解的所有最优解集训练为PSO-ELM代理模型,以实现所提策略的快速精确执行。最后,通过仿真验证了所提方法的有效性。算例表明所提策略可提升可再生能源的消纳率与系统变换器的利用率,并优化电能质量。
To address the issues of low renewable energy penetration and poor power quality in traditional source-network-load-storage (SNLS) systems
an optimum control scheme for an SNLS system embedded with a unified power quality conditioner (UPQC) is presented. The proposed scheme is implemented using the particle swarm optimization (PSO) based extreme learning machine (ELM) algorithm. In the multi-objective optimization operation scheme: the first optimization objective is to maximize the power generation of photovoltaic (PV) arrays; the second and third optimization objectives are to minimize the load voltage deviation and maximize the network side power factor
respectively; and the fourth optimization objective is to maximize the utilization rate of the converter. Since the multi-objective optimization problems are difficult to solve in real-time
a hierarchical optimization approach based on the priority order of optimization objectives is presented to simplify the multi-objective optimization problem into several single-objective ones. Then
by training all the optimum solution sets obtained as an PSO-ELM surrogate model
the proposed strategy can be executed quickly and accurately. Finally
the effectiveness of the proposed scheme is verified through simulations. The case studies show that the proposed strategy can improve the absorption rate of renewable energy and the utilization rate of converters
and optimize power quality.
0
浏览量
1
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构