随着风电渗透率的提高,双馈风电机组对电网频率的响应能力逐渐变弱,对于系统的频率稳定产生巨大影响。双馈风机单独调频能力不足以满足系统频率偏差要求,并且会产生弃风率高、能源利用率低的问题,为此将储能设备装设在双馈风机的并网侧,组成风储联合系统共同参与系统一次调频。文中通过利用风机的转子动能以及储能设备出力共同承担一次调频功率需求,提出基于风机转子转速以及荷电状态(State of Charge
the response ability of doubly-fed wind turbines to grid frequency gradually weakens
which has a huge impact on the frequency stability of the system.The independent frequency regulation capability of the doubly-fed wind turbines is currently insufficient to meet the frequency deviation requirements of the system
and it will result in high wind power permeability and low energy utilization rate.Therefore
energy storage equipment will be installed on the grid side of the doubly-fed wind turbines to form a wind storage joint system to participate in the primary frequency regulation of the system.In the article
a variable coefficient wind storage joint system based on the rotor speed and state of charge (SOC)is proposed to participate in the primary frequency regulation control strategy by utilizing the rotor kinetic energy of the wind turbine and the output of the energy storage equipment to jointly undertake the primary frequency regulation power demand.The doubly-fed wind turbine responds to the virtual inertia link by releasing or absorbing its own rotor kinetic energy
and dynamically adjusts the virtual inertia coefficient through its own rotor speed
andthe energy storage device dynamically adjusts the virtual droop coefficient based on its own state of charge to participate in the frequency response droop process.Finally
by building a simulation model to compare the frequency modulation effects of variable coefficient method
fixed coefficient method
and wind power independent frequency modulation under step load disturbance and continuous load disturbance
it is verified that the control strategy in the article can effectively reduce system frequency deviation.At the same time
the doubly-fed wind turbine can fully utilize its inherent rotor kinetic energy
and the energy storage equipment can also output smoothly