韩中合, 李晨, 李恒凡. 严寒条件空冷塔迎风冷却三角临界防冻特性研究[J]. 热力发电, 2026,(9).
韩中合, 李晨, 李恒凡. 严寒条件空冷塔迎风冷却三角临界防冻特性研究[J]. Thermal Power Generation, 2026, (9).
韩中合, 李晨, 李恒凡. 严寒条件空冷塔迎风冷却三角临界防冻特性研究[J]. 热力发电, 2026,(9). DOI: 10.19666/j.rlfd.202601052.
韩中合, 李晨, 李恒凡. 严寒条件空冷塔迎风冷却三角临界防冻特性研究[J]. Thermal Power Generation, 2026, (9). DOI: 10.19666/j.rlfd.202601052.
【目的】为探究间接空冷塔在冬季严寒条件下的防冻性能,保障火电厂冬季安全经济运行。【方法】基于计算流体力学建立了迎风空冷三角临界防冻系统的数学模型,通过耦合多孔介质模型和分布参数法,实现了对迎风侧与背风侧换热特性的分区量化分析,得到了不同环境风速风温和入口水温下冷却三角临界循环水流速和临界百叶窗开度,揭示了临界状态下各区块换热性能的变化趋势。【结果】结果表明:沿着水流动方向,各段出口水温持续下降。在背风侧,各区域进出口水温差先缓慢增长后趋于减小,而在迎风侧逐渐降低。风速升高、环境温度和散热器入口水温降低,迎风冷却三角循环水流速临界值增加,临界百叶窗开度减小;随着散热器入口水温的增加,临界循环水流速先迅速下降,后趋于平稳,并且在低入口水温工况下,环境温度对临界循环水流速影响更大,在环境风速7 m/s、入口水温5℃的情况下,临界循环水流速在环境温度-10℃和-35℃时分别为2.27 m/s和10 m/s。临界水流速工况下,迎风侧区块的换热系数大于背风侧,背风侧区块的换热系数先上升后下降,迎风侧区块的换热系数先减小后上升。在临界开度工况下,当临界开度较大时,换热系数较高,且迎风侧大于背风侧;而当开度进一步减小接近全关状态时,换热系数逐渐降低,迎风侧和背风侧换热系数均呈现先减少后增大的趋势。【结论】该结果可为类似寒冷地区间接空冷系统的防冻设计和运行策略制定提供参考。
[Objective] This study aims to investigate the anti-freezing performance of indirect air-cooled towers under severe winter conditions and ensure the safe and economical operation of thermal power plants. [Methods] A mathematical model of the critical anti-freezing system for windward air-cooled triangular units was developed based on computational fluid dynamics. By coupling a porous media model with the distributed parameter method
a partitioned quantitative analysis of the heat transfer characteristics on the windward and leeward sides was conducted. The study determined the critical circulating water velocity and critical louver opening for the cooling cell under various ambient wind speeds
ambient temperatures
and inlet water temperatures
revealing the variation trends in sector heat transfer performance under critical conditions. [Results] The results indicate that the outlet water temperature of each section continuously decreases along the flow direction. On the leeward side
the temperature difference across sections initially increases slowly before decreasing
while on the windward side
it gradually decreases. A decrease in the radiator inlet water temperature
a decrease in ambient temperature
and an increase in wind speed all contribute to a higher freezing risk for the tube bundle. This leads to an increase in the critical water velocity and a decrease in the critical louver opening. As the inlet water temperature rises
the critical water velocity first decreases rapidly and then stabilizes. The influence of ambient temperature on the critical circulating water velocity is more pronounced under low inlet water temperature conditions. For example
at an ambient wind speed of 7 m/s and an inlet water temperature of 5 ℃
the critical velocities are 2.27 m/s and 10 m/s at ambient temperatures of-10 ℃ and-35 ℃
respectively. Under conditions near the critical water velocity
the heat transfer coefficient is higher for windward sectors than for leeward sectors. On the leeward side
the coefficient first increases and then decreases
while on the windward side
it first decreases and then increases. Under conditions near the critical opening
a larger critical opening corresponds to a higher heat transfer coefficient
with the windward side exhibiting a greater value than the leeward side. When the opening is further reduced
approaching a fully closed state
the heat transfer coefficient gradually decreases. Both the windward and leeward side coefficients show a trend of initially decreasing and then increasing. [Conclusion] In conclusion
this study provides a detailed analysis of the critical anti-freezing operational parameters for windward cooling cells
offering valuable insights for the anti-freezing design and operational strategy development of similar indirect air-cooled systems in cold regions.