1. 华电莱州发电有限公司
2. 电站能量传递转化与系统教育部重点实验室(华北电力大学)
纸质出版:2026
移动端阅览
耿新博, 史利强, 王洪, 等. 考虑分时电价的燃煤电站直流冷却系统优化运行研究[J]. 热力发电, 2026,(9).
耿新博, 史利强, 王洪, et al. 考虑分时电价的燃煤电站直流冷却系统优化运行研究[J]. Thermal Power Generation, 2026, (9).
耿新博, 史利强, 王洪, 等. 考虑分时电价的燃煤电站直流冷却系统优化运行研究[J]. 热力发电, 2026,(9). DOI: 10.19666/j.rlfd.202512032.
耿新博, 史利强, 王洪, et al. 考虑分时电价的燃煤电站直流冷却系统优化运行研究[J]. Thermal Power Generation, 2026, (9). DOI: 10.19666/j.rlfd.202512032.
【目的】现货市场的电价波动会影响燃煤机组的运行成本,现有模型难以及时反映电价变化对机组运行经济性的影响。【方法】针对电价波动影响经济性的问题,本文基于某1 000 MW燃煤机组,构建了包含负荷水平、冷源特性与电价波动的多变量决策模型,提出一种结合分时电价信息的直流冷却系统运行方式优化策略,分别评估了不同季节下的最优调控方案。【结果】研究结果表明:在电价低谷适当提高凝汽器背压、减少循环水泵的台数及转速,有助于降低水泵电耗并提高收益;而在高温、高负荷以及电价高峰期,保持较低背压以增大机组出力,可提高收益。冬季冷端优化使机组在电价低谷时期收益提高5 670.13元,电价高峰时期收益提高了242.08元,单日收益增加5 912.27元;夏季优化使机组在电价低谷时期收益提高2 861.69元,电价高峰时期收益提高了2 226.76元,单日收益提升达5 088.46元。【结论】该结果验证了考虑分时电价的冷端协同优化在电力系统灵活性调度中的可行性,为开展冷端系统智能化改造和运行优化提供了技术支撑。
[Objective] In the contemporary electricity spot market
the continuous fluctuation of electricity prices has become a critical factor influencing the operational costs and overall economic viability of coal-fired power generating units. Conventional optimization models for power plant operations typically focus on thermodynamic efficiency or coal consumption rates in isolation
which makes it difficult to reflect the real-time impact of dynamic electricity price changes on the actual profitability of the unit. [Methods] To address the challenge of economic sensitivity to price volatility
this research proposes a novel operational optimization strategy for once-through cooling systems that explicitly integrates time-of-use electricity price signals. This strategy dynamically balances coal consumption cost and circulating water pump power consumption
ensuring the unit achieves maximum net revenue while meeting required heat exchange performance requirements. Using empirical data collected from a 1 000 MW coal-fired unit between July 2024 and August 2025
alongside local time-of-use electricity price curves
this study constructs a comprehensive multivariate decision-making model. This model incorporates critical variables such as unit load levels
cold source environmental characteristics
and market price fluctuations to evaluate and determine the optimal control schemes across various seasonal conditions. [Results] The research findings indicate a significant shift in optimal operational logic depending on market conditions. Specifically
during periods of price troughs
it is more economically advantageous to appropriately increase the condenser backpressure by reducing the number of active circulating water pumps or adjusting their rotational speeds. This approach prioritizes the reduction of auxiliary power consumption over marginal gains in generation efficiency
thereby enhancing the net financial return when the market value of electricity is low. Conversely
during periods of high ambient temperatures
high load demands
or peak electricity prices
the model suggests maintaining a lower backpressure to maximize the unit's power output
thereby capturing higher market returns. Seasonal empirical analysis shows that in winter
this cold-end optimization increases revenue by 5 670.13 yuan during low-price periods and 242.08 yuan during peak periods
resulting in a total daily revenue gain of 5 912.27 yuan. In summer
the optimization yields a revenue increase of 2 861.69 yuan during low-price periods and 2 226.76 yuan during peak periods
with a total daily enhancement of 5 088.46 yuan. [Conclusion] These findings validate the feasibility of collaborative cold-end optimization considering time-of-use prices within the framework of flexible power system dispatch. This study provides significant technical support for the intelligent transformation and operational optimization of cooling systems
enhancing the market competitiveness of coal-fired units in a fluctuating economic landscape.