ZHANG Wenxiang, YAN Haineng, SUN Zhijun, et al. Analysis and treatment of difficulties in NOx emission control of a supercritical 660 MW circulating fluidized bed boiler[J]. Thermal power generation, 2024, 53(5): 109-114.
ZHANG Wenxiang, YAN Haineng, SUN Zhijun, et al. Analysis and treatment of difficulties in NOx emission control of a supercritical 660 MW circulating fluidized bed boiler[J]. Thermal power generation, 2024, 53(5): 109-114. DOI: 10.19666/j.rlfd.202401010.
It is difficult to control NO_x emissions during full load operation of a 660 MW supercritical circulating fluidized bed(CFB) boiler in a certain power plant
and its instantaneous value is prone to exceed the ultra-low emission limit. In addition
the selective non-catalytic reduction(SNCR) system has a high ammonia consumption and severe ammonia escape issues. To solve these problems
on-site experiments on NO_x original emissions
SNCR denitrification efficiency
CO mass concentration and bottom slag combustibles were conducted
and optimization experiments on secondary air volume layout were also performed. It was found that
the original NO_x emissions of the CFB boiler were relatively low
with a maximum of 120 mg/m~3(standard condition) during full load operation and a NO_x mass concentration below 50 mg/m~3 during medium and low loads. However
there was a significant deviation in NO_x mass concentration between the front and rear ends of the furnace
and the NO_x in flue gas was mainly generated in front of the furnace. The reason why NO_x emissions are difficult to control is due to the low denitrification efficiency of SNCR and uneven coal feeding in the furnace. The SNCR denitrification efficiency at inlet of the 6 separators was all below 50%
among which the denitrification efficiency of four separators B
C
E
and F was below 40%. Furthermore
according to the distribution of parameters in the furnace depth direction
such as the bed temperature
the content of combustible materials in bottom slag
and the variation of CO mass concentration
it can be determined that the uniformity of coal feeding in the furnace also had a significant effect on the control of NO_x emissions at full load. Currently
the power plant cannot achieve uniform coal feeding without renovation
but the original NO_x generation can be reduced by adjusting the secondary air volume ratio in the depth direction of the furnace