DONG Wei, LYU Meng, MEI Long, et al. Comprehensive optimization of slag cooler and air heater system in a 350 MW circulating fluidized bed boiler unit[J]. Thermal power generation, 2022, 51(5): 81-88.
DONG Wei, LYU Meng, MEI Long, et al. Comprehensive optimization of slag cooler and air heater system in a 350 MW circulating fluidized bed boiler unit[J]. Thermal power generation, 2022, 51(5): 81-88. DOI: 10.19666/j.rlfd.202110228.
Aiming at solving the problems of low efficiency of slag cooler's waste heat utilization system and large heat consumption of air heater in current circulating fluidized bed(CFB) boiler units
a comprehensive optimization system for slag cooler and air heater system is proposed. Taking a typical 350 MW CFB boiler unit as an example
the thermal performance of the optimized system under different working conditions is analyzed in detail. On this basis
the energy saving effect of the optimized system at different ambient temperatures in winter is calculated
and its economic performance is explored. The results show that
taking the case unit as an example
under the condition that the available residual heat of the slag cooler remains unchanged
the power generation coal consumption rate of the unit applying the optimized system in winter can reduce by 2.0 g/(kW·h)
and that in other seasons can reduce by 0.9 g/(kW·h). The average annual net income of the unit can increase by 2.71 million yuan
and both the energy saving effect and economic benefits are significant. In addition
the energy saving effect of the optimized system in winter will be more significant when the ambient temperature is lower.