LIANG Danxi, DENG Zhanfeng, CUI Shuangshuang, et al. Dynamic characteristics of liquefied air energy storage system participating in frequency regulation of power grid[J]. Thermal power generation, 2020, 49(8): 104-110.
LIANG Danxi, DENG Zhanfeng, CUI Shuangshuang, et al. Dynamic characteristics of liquefied air energy storage system participating in frequency regulation of power grid[J]. Thermal power generation, 2020, 49(8): 104-110. DOI: 10.19666/j.rlfd.202005122.
To deeply study the dynamic characteristics of liquefied air energy storage system participating in frequency regulation of the power grid
the simulation model of the expansion system of a 12.5 MW liquefied air energy storage was established based on the mathematical model. Combined with the infinite grid model
the parameter changes of the energy storage system under no-load impulse
grid connection and frequency regulation were simulated
and the feasibility and dynamic characteristics of the liquefied air energy storage system as a new auxiliary power grid frequency regulation technology were analyzed. The simulation results show that
the maximum unit value of the expander rotor speed during no-load impulse is 1.013
and the overspeed ratio is 1.3%.During grid-connected power generation
the actual speed unit value and the actual electric power unit value are stable to 1 at 765 s. In the process of grid frequency regulation
the actual power unit value stabilizes to 0.990 within10 s
and the highest actual power unit value is 1.032. This study provides a data reference for understanding the dynamic characteristics of liquefied air energy storage systems participating in grid frequency regulation.