YANG Danlei, TANG Guihua, FAN Yuanhong, et al. Cooling wall arrangement and wall temperature characteristic analysis for supercritical carbon dioxide coal-fired boiler with flue gas recirculation[J]. Thermal power generation, 2020, 49(10): 144-150.
YANG Danlei, TANG Guihua, FAN Yuanhong, et al. Cooling wall arrangement and wall temperature characteristic analysis for supercritical carbon dioxide coal-fired boiler with flue gas recirculation[J]. Thermal power generation, 2020, 49(10): 144-150. DOI: 10.19666/j.rlfd.202004113.
The supercritical carbon dioxide(S-CO_2) Brayton cycle has attracted wide attentions owing to its high efficiency and compactness. However
for large scale(around 1 000 MW) S-CO_2 coal-fired power plants
the high S-CO_2 inlet temperature coupled with high combustion heat flux will induce the cooling wall overheating. In the present work
the coupled model between the furnace combustion and the S-CO_2 heat transfer is developed for the cooling wall thermal safety analysis. In one-dimensional calculation of the circumferential average cooling wall temperature
the flue gas recirculation method is introduced to reduce the cooling wall temperature
and the onedimensional cooling wall counter flow arrangement is further proposed. Moreover
the three-dimensional cooling wall temperature distribution is examined
and the spiral cooling wall is further introduced to reduce the circumferential hot spot temperature. The results show that
the optimization methods in the present work can effectively reduce the cooling wall temperature and eliminate the local hot spot
which can provide guidance for the engineering design of large scale S-CO_2 boilers.