CHEN Jie. Analysis and comprehensive prevention of fracture damage in condenser heat exchanger tube[J]. Thermal power generation, 2019, 48(6): 115-120.
CHEN Jie. Analysis and comprehensive prevention of fracture damage in condenser heat exchanger tube[J]. Thermal power generation, 2019, 48(6): 115-120. DOI: 10.19666/j.rlfd.201901039.
凝汽器换热管断裂损伤分析与综合防治
摘要
凝汽器是电站汽轮机组中重要的换热设备
换热管断裂损伤是其主要故障模式
严重影响机组可靠运行。本文针对某电站凝汽器故障问题
通过分析换热管调试阶段和商业运行阶段的断裂损伤情况
逐一排查可能的致伤原因
最后确定此次事故为流体弹性激振诱发的疲劳断裂
而厂家对凝汽器设计的安全裕度考虑不足
理论设计与现场实际产生了偏差
是导致换热管发生非预期断裂损坏的根本原因。针对换热管断裂损伤时的运行工况和损伤区域
提出加装防振条、局部区域预防性堵管、仿真计算与应变测量等一系列综合防治措施
可有效降低换热管断裂损伤的风险
提高凝汽器设备的可靠性。
Abstract
Condenser is an important heat exchanger device in power plant steam turbines
and fracture damage of heat exchanger tube is its main failure mode
which seriously affects the reliable operation of the unit. Aiming at solving the problem of condenser failure in a power station
by analyzing the fracture damage of the heat exchanger tube during commissioning and commercial operation stages
the possible causes of the damage are investigated one by one. Finally
the fatigue fracture induced by hydro elastic excitation is considered as the major reason. In fact
the safety margin of the condenser design is insufficiently considered by the manufacturer
and the deviation between theoretical design and field practice results is the primary cause for the unexpected fracture damage. Against the operation condition and damage area of the heat exchanger tube when it is damaged by fracture
a series of comprehensive prevention measures are put forward
such as installing the anti-vibration strip and preventive blockage in local area
and carrying out simulation calculation and strain measurement
which can effectively reduce the risk of the heat exchanger tube fracture damage and improve the reliability of condenser equipment.