ZHOU Junbo, LIU Xi, ZHANG Hua, et al. Control characteristic analysis of typical coal-fired boilers during low load or variable load running[J]. Thermal power generation, 2018, 47(9): 34-40.
ZHOU Junbo, LIU Xi, ZHANG Hua, et al. Control characteristic analysis of typical coal-fired boilers during low load or variable load running[J]. Thermal power generation, 2018, 47(9): 34-40. DOI: 10.19666/j.rlfd.201803071.
To improve the flexibilities of coal-fired boilers
the subcritical and supercritical front and rear wall opposed coal-fired boilers and subcritical and ultra-supercritical tangentially coal-fired boilers are selected as research objects to carry out experiments. Through low load running test of three boilers and variable load disturbance test of one boiler
the control characteristics and regulating quality of main parameters during low load and variable load running of four typical coal-fired boilers are compared and analyzed. The results show that
the lowest load of stable combustion of boilers with different structures without oil can reach 17%Pe~25%Pe. The boiler with large capacity has better performance of steady combustion with the lowest load. The main steam pressure
main steam temperature and reheat steam temperature decrease rapidly with the load reduction of boilers. As the boiler load decreases
the excess air coefficient increases
and the increment of fuel NO_x is much larger than that of thermal NO_x
causing the change trend of NO_x concentration is generally opposite to that of boiler load.