WANG Zhaoguo, ZHANG Chao, LI Dongyang, et al. Experiment of energy saving and optimization on electrostatic precipitator system in ultra-low emission coal-fired power plants[J]. Thermal power generation, 2018, 47(3): 109-114.
WANG Zhaoguo, ZHANG Chao, LI Dongyang, et al. Experiment of energy saving and optimization on electrostatic precipitator system in ultra-low emission coal-fired power plants[J]. Thermal power generation, 2018, 47(3): 109-114. DOI: 10.19666/j.rlfd.201709099.
燃煤电厂超低排放除尘系统节能优化试验
摘要
在国内大部分燃煤电厂已完成超低排放改造的新形势下
环保设备运行能耗偏高
运行调整方式不灵活等问题凸显
节能降耗成为今后一段时间燃煤机组的研究热点。本文通过对电除尘器进行能耗分析
提出了一系列节能优化运行措施
并对某燃煤电厂超超临界680 MW机组电除尘系统进行节能优化试验
节能优化实施后整个电除尘系统厂用电率从0.378%降至0.256%
节电率达到32.32%
而烟尘排放质量浓度仅从1.62 mg/m3增至3.17 mg/m3
在实现该机组烟尘稳定超低排放的同时
降低了运行能耗。该试验结果可为其他机组的节能优化运行提供了参考。
Abstract
Under the new situation that most domestic coal-fired power plants have completed the ultra-low emission transformation
some new problems highlight
such as higher running energy consumption of environmental protection equipment
less flexible of operation adjustment method and so on. Therefore
energy saving of coal-fired unit will be a research hotspot in the future. Based on the energy consumption analysis of electrostatic precipitator
this study puts forward a series of energy saving and optimization measures. The experiment of energy saving and optimization on electrostatic precipitator system is carried out on the 680 MW unit of a coal-fired power plant. The results show that the electricity consumption rate of the entire ESP system after energy saving and optimization drops from 0.378% to 0.256% and power saving rate reaches 32.32%
while the dust emission concentration increases from 1.62 mg/m3 to 3.17 mg/m3. This illustrates that this unit realizes ultralow emission and reduces the running energy consumption. The experimental results provide some reference for other units of the energy saving and optimization.