WU Wen-long1, LI Chang-ming1, CHANG Jian-bing1, et al. KEEPING VIGILANT OVER TUBE-BURST CAUSED BY ACID CLEANING OF BOILERS[J]. Thermal power generation, 2008, 37(12): 54-56.
WU Wen-long1, LI Chang-ming1, CHANG Jian-bing1, et al. KEEPING VIGILANT OVER TUBE-BURST CAUSED BY ACID CLEANING OF BOILERS[J]. Thermal power generation, 2008, 37(12): 54-56. DOI: 10.19666/j.rlfd.2008.12.014.
警惕锅炉酸洗不当引起的爆管事故
摘要
某电厂600 MW机组直流锅炉酸洗月余后起动中
垂直水冷壁水汽转化过渡区多处发生过热超温爆管。用内窥镜检查确认
管子内壁相应部位存在大量固体混杂沉积物是爆管的直接原因。对此
分析确认沉积物主要是锅炉起动前化学清洗的残留物
起动时未能将其冲净
起动后这些残留物随汽水循环迁移至水汽转化过渡区
并在扰流部位沉积加剧。
Abstract
In start-up process after more than one month of acid cleaning for once-through boiler of 600 MW unit in one power plant
over-temperature tube-burst due to short-term superheating has occurred at many places in the transition zone of water-steam conversion on the vertical water-wall.It is believed through inspection by using an endoscope that the direct cause resulting in tube-burst is large amount of mixed solid deposits accumulated on corresponding positions of the inner surface.For this
it is affirmed through analysis that the deposits are mainly the residual impurities of chemical cleaning before starting-up
and being not flushed away during the starting-up.After start-up
these residual impurities moved along with steam-water cycle to the transition zone of water-steam conversion
and strengthened deposition in the turbulent positions may exist.