MA Kai-zhong Yangzhou Power Generation Co Ltd No.2. FEED-WATER REGULATION OF SUPERCRITICAL BOILERS[J]. Thermal power generation, 2007, (9): 53-56. DOI: 10.19666/j.rlfd.2007.09.015.
Combining with concrete example of a boiler feed-water control system in the start-up system with built - in boiler water circulatory pump for one 600 MW supercritical unit
and based on analysis of feed-water regulating process in the full load range
a typical four-loop feed-water control system and its working principle have been presented
the said system controls fuel/water ratio by using heat absorption and enthalpy increase of the evaporator
and corrects fuel/water ratio by using the enthalpy value at outlet of the separater
as well as correcting feed-water flow rate by using the temperature decrease of the first-stage desuperheater.