WANG Chunchang, YANG Shumin, ZHANG Yizheng et al. CAUSE ANALYSIS FOR SOMEWHAT LOW INDICATING VALUE OF THE FLAME DETECTOR OR MISJUDGEMENT OF THE VALUE AND RESOLVING MEASURES THEREOF[J]. Thermal power generation, 2006, (9): 21-23.
WANG Chunchang, YANG Shumin, ZHANG Yizheng et al. CAUSE ANALYSIS FOR SOMEWHAT LOW INDICATING VALUE OF THE FLAME DETECTOR OR MISJUDGEMENT OF THE VALUE AND RESOLVING MEASURES THEREOF[J]. Thermal power generation, 2006, (9): 21-23. DOI: 10.19666/j.rlfd.2006.09.007.
火焰检测器指示值偏低或误判的原因分析及解决措施
摘要
分析了电站燃煤锅炉个别燃烧器火检指示值偏低或误判的原因
提出了调整火检的检测距离
消除火检视线遮挡
以及修改火检的临界值和背景值等解决措施。日照电厂2台锅炉的应用实践表明
在煤粉气流稳定着火燃烧的情况下
调整火检的检测距离不仅可解决个别火检指示值偏低的问题
而且可节省大量的稳燃油
经济效益显著。
Abstract
The causes leading to somewhat low indicating value of the flame detector for very few burners in coalfired utility boiler or misjudgement of the value have been analysed
and resolving measures
such as adjusting the detection distance of the flame detector
eliminating shield of vision for the flame detector
revising the critical value and background evaluation etc.
being put forward. Practice of application on two boilers in Rizhao Power plant shows that the adjustment of detection distance not only can solve the problem of somewhat low indicating value for very few flame detectors
but also can save large amount of fuel oil used for stabilizing combustion
having remarkable economic benefit under condition of stable ignition and combustion for pulverized coal and air flow.