CONTROL OF WATER-DROPPING NOISE AND ENHANCEMENT OF COOLING EFFETIVENESS FOR CROSS-FLOW TYPE NATURAL DRAFT COOLING TOWER[J]. Thermal power generation, 2006, (3): 52-53.
CONTROL OF WATER-DROPPING NOISE AND ENHANCEMENT OF COOLING EFFETIVENESS FOR CROSS-FLOW TYPE NATURAL DRAFT COOLING TOWER[J]. Thermal power generation, 2006, (3): 52-53. DOI: 10.19666/j.rlfd.2006.03.016.
The situation of controlling noise of 1750 m2 cross-flow type natural draft cooling tower by adopting HTB-80-33 tricking fillers in Huadian Banshan Power-Generation Co Ltd in Hangzhou City has been presented. After retrofitting not only the water-dropping noise of the cooling tower has been reduced 13 dB
but also the outlet water temperature being lowered by 2.82 ℃