BI Fa sen. CAUSE ANALYSIS OF QUALITY DETERIORATION FOR FIRE RESISTANT OIL USED IN YIMIN POWER PLANT AND COUNTERMEASURES THEREOF[J]. Thermal power generation, 2004, (7): 68-70.
BI Fa sen. CAUSE ANALYSIS OF QUALITY DETERIORATION FOR FIRE RESISTANT OIL USED IN YIMIN POWER PLANT AND COUNTERMEASURES THEREOF[J]. Thermal power generation, 2004, (7): 68-70. DOI: 10.19666/j.rlfd.2004.07.020.
伊敏发电厂抗燃油油质劣化分析及对策
摘要
对伊敏发电厂抗燃油电阻率偏低造成伺服阀腐蚀及EH油泵出口滤网频繁报警问题进行了分析
找出原因后采用国电热工研究院生产的强极性硅铝再生装置对抗燃油进行处理
并辅以更换滤网、提高运行油温以及消除抗燃油系统局部过热点等措施
使问题得以解决
Abstract
The problems resulting from quality deterioration of fire resistant oil
such as corrosion of the servo valve due to resistivity of the said oil being somewhat lower
and warning from the outlet strainer of EH Type oil pump being frequently occurred in Yimin Power Plant
have been analysed. After finding out the causes
the said fire resistant oil has been treated using the strong palarity silicon aluminium regenerative facility manufactured by The Thermal Power Research Institute under State Power Corp
and complementary measures
namely replacing the strailler
enhancing oil temperature in operation
and eliminating local overheat points in the fire resistant oil system
have been taken to make the said problems to have been resolved.