王振国, 刘黎, 周啸宇, et al. Cause Analysis of a 500 kV Transmission Line Tower Collapse Icurred by Downburst[J]. 2021, 40(11): 16-22. DOI: 10.19585/j.zjdl.202111003.
Strong breeze is a major natural disaster that leads to transmission line collapse. In order to reveal the causes of a transmission line tower collapse
the paper recaptures the transmission line fault and damage process based on the field investigation results
data collected by weather surveillance radar and analysis results from the mechanical model of the tower. The analysis results show that the disaster
characterized by discontinuity
multiple scales and small spatial-temporal scale of a strong disaster
tallies with the typical features of downburst in severe convective wind gust which is the direct cause of the collapse. The conclusion of fault analysis can provide a useful reference for the subsequent fault analysis under the same type of wind disaster and the study of transmission line failure mechanism under the action of a downburst.