Effect of Interface Charge on Partial Discharge Characteristics of Oil-Pressboard Insulation in Non-Uniform AC/DC Combined Electric Field Under Different Temperatures
Regular Papers|更新时间:2026-06-12
|
Effect of Interface Charge on Partial Discharge Characteristics of Oil-Pressboard Insulation in Non-Uniform AC/DC Combined Electric Field Under Different Temperatures
Effect of Interface Charge on Partial Discharge Characteristics of Oil-Pressboard Insulation in Non-Uniform AC/DC Combined Electric Field Under Different Temperatures
中国电机工程学会电力与能源系统学报(英文)2026年12卷第3期 页码:1598-1607
作者机构:
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University,Beijing,China
Chunjia Gao, Bo Qi, Chengrong Li. Effect of Interface Charge on Partial Discharge Characteristics of Oil-Pressboard Insulation in Non-Uniform AC/DC Combined Electric Field Under Different Temperatures[J]. 中国电机工程学会电力与能源系统学报(英文), 2026,12(3):1598-1607.
Chunjia Gao, Bo Qi, Chengrong Li. Effect of Interface Charge on Partial Discharge Characteristics of Oil-Pressboard Insulation in Non-Uniform AC/DC Combined Electric Field Under Different Temperatures[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1598-1607.
Chunjia Gao, Bo Qi, Chengrong Li. Effect of Interface Charge on Partial Discharge Characteristics of Oil-Pressboard Insulation in Non-Uniform AC/DC Combined Electric Field Under Different Temperatures[J]. 中国电机工程学会电力与能源系统学报(英文), 2026,12(3):1598-1607. DOI: 10.17775/CSEEJPES.2023.09040.
Chunjia Gao, Bo Qi, Chengrong Li. Effect of Interface Charge on Partial Discharge Characteristics of Oil-Pressboard Insulation in Non-Uniform AC/DC Combined Electric Field Under Different Temperatures[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1598-1607. DOI: 10.17775/CSEEJPES.2023.09040.
Effect of Interface Charge on Partial Discharge Characteristics of Oil-Pressboard Insulation in Non-Uniform AC/DC Combined Electric Field Under Different Temperatures
摘要
Abstract
The investigation of partial discharge characteristics within oil-pressboard insulation systems is pivotal for the operational integrity of converter transformers. This research scrutinizes the substantial influence of thermal conditions on partial discharge (PD) attributes
with a focus on delineating the temperature-dependent variations in PD behaviors of oil-pressboard insulation under asymmetric AC/DC electrostatic fields. Additionally
this study delves into the intricate role of interface charge accumulation and its consequential impact on PD dynamics. Empirical observations underscore that an ambient temperature escalation from 20°C to 80°C precipitates a notable decrease in the Partial Discharge Inception Voltage (PDIV) and surface flashover thresholds by 72.7% and 9.94%
respectively. This thermal elevation also catalyzes an augmentation in key PD parameters
encompassing discharge recurrence frequency and aggregate discharge intensities. Significantly
the study identifies an ‘attenuation effect’ induced by interface charges on PD traits. Elevated thermal conditions attenuate both the superficial and volumetric resistivity of oil-pressboard insulation
thereby diminishing its dielectric robustness and curtailing interface charge build-up. This scenario aggravates PD progression. The synergistic interplay between interface charge dynamics and the resistivity attributes of the oil-pressboard matrix elucidates the thermal sensitivity of PD phenomena. These findings contributes to a deeper understanding of the thermal modulation of PD in oil-pressboard systems
offering critical insights for the refinement of insulation design and the optimization of electrical strength testing methodologies pertinent to such insulation matrices.