Integrated Multiport Flexible Voltage Clamp Circuit Breaker with DC Chopper Applied to MMC-HVDC System
Regular Papers|更新时间:2026-03-25
|
Integrated Multiport Flexible Voltage Clamp Circuit Breaker with DC Chopper Applied to MMC-HVDC System
Integrated Multiport Flexible Voltage Clamp Circuit Breaker with DC Chopper Applied to MMC-HVDC System
中国电机工程学会电力与能源系统学报(英文)2026年12卷第1期 页码:352-365
作者机构:
Key Laboratory of Modern Power System Simulation and Control, Renewable Energy Technology Ministry of Education, Northeast Electric Power University,Jilin,China
Guoqing Li, Yuheng Song, Jing Bian, 等. Integrated Multiport Flexible Voltage Clamp Circuit Breaker with DC Chopper Applied to MMC-HVDC System[J]. 中国电机工程学会电力与能源系统学报(英文), 2026,12(1):352-365.
Guoqing Li, Yuheng Song, Jing Bian, et al. Integrated Multiport Flexible Voltage Clamp Circuit Breaker with DC Chopper Applied to MMC-HVDC System[J]. CSEE Journal of Power and Energy Systems, 2026, 12(1): 352-365.
Guoqing Li, Yuheng Song, Jing Bian, 等. Integrated Multiport Flexible Voltage Clamp Circuit Breaker with DC Chopper Applied to MMC-HVDC System[J]. 中国电机工程学会电力与能源系统学报(英文), 2026,12(1):352-365. DOI: 10.17775/CSEEJPES.2023.06350.
Guoqing Li, Yuheng Song, Jing Bian, et al. Integrated Multiport Flexible Voltage Clamp Circuit Breaker with DC Chopper Applied to MMC-HVDC System[J]. CSEE Journal of Power and Energy Systems, 2026, 12(1): 352-365. DOI: 10.17775/CSEEJPES.2023.06350.
Integrated Multiport Flexible Voltage Clamp Circuit Breaker with DC Chopper Applied to MMC-HVDC System
the protection equipment of power grids must be improved during the fault period. This study proposes an integrated multiport flexible voltage clamp circuit breaker with a DC chopper acting on the receiving end converter to solve the DC short circuit fault and surplus power because of AC low-voltage fault; it has a modular design. As a DC circuit breaker
the device utilizes the voltage-clamping principle and thyristor semi-control to remove faults. As the fault current increases
the branch circuit outputs different voltage levels by selecting different gears
thereby controlling the voltage-clamping effect. This device can distinguish between different fault types to prevent secondary shocks in the system. As a DC chopper
the voltage at both ends of the energy dissipation resistor is varied by switching submodules
consuming surplus power to complete AC low-voltage faults and minimizing the impact of low-voltage faults on the system's transmission capacity. Finally
the effectiveness and applicability of the equipment are verified using wind turbines connected to a flexible DC transmission three-terminal power grid model in PSCAD/EMTDC
and two fault simulation types are analyzed. A comparison of the electrical quantities (fault current
system voltage and branch voltage) of the proposed circuit breaker with other similar equipment shows that due to the efficiency of the proposed equipment
the peak fault current is reduced by at least 35.8%. The required voltage stress of key power electronic equipment is reduced by at least 71.5%. Therefore
the equipment ensures that the per-unit voltage of the DC system does not exceed 1.05 during AC fault crossing.