Chunyi Guo, Quan Ye, Xiuyu Chen, 等. Subsequent Commutation Failure Suppression Control for LCC-HVDC System Based on Fuzzy Clustering[J]. 中国电机工程学会电力与能源系统学报(英文), 2026,12(5):2415-2424.
Chunyi Guo, Quan Ye, Xiuyu Chen, et al. Subsequent Commutation Failure Suppression Control for LCC-HVDC System Based on Fuzzy Clustering[J]. CSEE Journal of Power and Energy Systems, 2026, 12(5): 2415-2424.
Chunyi Guo, Quan Ye, Xiuyu Chen, 等. Subsequent Commutation Failure Suppression Control for LCC-HVDC System Based on Fuzzy Clustering[J]. 中国电机工程学会电力与能源系统学报(英文), 2026,12(5):2415-2424.DOI: 10.17775/CSEEJPES.2022.05740.
Chunyi Guo, Quan Ye, Xiuyu Chen, et al. Subsequent Commutation Failure Suppression Control for LCC-HVDC System Based on Fuzzy Clustering[J]. CSEE Journal of Power and Energy Systems, 2026, 12(5): 2415-2424.DOI: 10.17775/CSEEJPES.2022.05740.
Subsequent Commutation Failure Suppression Control for LCC-HVDC System Based on Fuzzy Clustering
摘要
Abstract
Line-commutated converter-based high voltage direct current (LCC-HVDC) may experience subsequent commutation failure (SCF) following a first commutation failure (CF). The SCF could create a series of serious disturbances to the AC grid and DC system
which may lead to large power reduction or even system instability issues. To prevent its occurrence
this paper proposes an SCF suppression control strategy based on fuzzy clustering and identification approach. First of all
the similar dynamic behavior of DC side electrical quantities in different types of AC faults at the inverter side is revealed and validated by theoretical analysis and simulation. Then
transient response information of the selected DC side electrical quantities at the rectifier side is collected in an offline preset specific AC fault. To identify the inverter transient stage
a mapping relationship between the selected DC side electric quantities during the transient stages of the preset fault conditions is established by the fuzzy c-means (FCM) clustering algorithm. Finally
an approach to inhibit SCF by directly adjusting the firing angle at the rectifier side is proposed based on the mapping relationship. Simulation results show the proposed control method
which is realized by detecting the local DC-side electrical quantities at the rectifier side and quickly identifying the transient stage of the inverter
can effectively inhibit SCF by directly regulating the rectifier firing angle.