Yuansheng Liang, Zhanpeng Xu, Haifeng Li, 等. Improved Control Strategy of Soft Open Points for Distribution Network with High Penetration of Distributed Generation[J]. 中国电机工程学会电力与能源系统学报(英文), 2026,12(3):1335-1347.
Yuansheng Liang, Zhanpeng Xu, Haifeng Li, et al. Improved Control Strategy of Soft Open Points for Distribution Network with High Penetration of Distributed Generation[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1335-1347.
Yuansheng Liang, Zhanpeng Xu, Haifeng Li, 等. Improved Control Strategy of Soft Open Points for Distribution Network with High Penetration of Distributed Generation[J]. 中国电机工程学会电力与能源系统学报(英文), 2026,12(3):1335-1347. DOI: 10.17775/CSEEJPES.2022.03170.
Yuansheng Liang, Zhanpeng Xu, Haifeng Li, et al. Improved Control Strategy of Soft Open Points for Distribution Network with High Penetration of Distributed Generation[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1335-1347. DOI: 10.17775/CSEEJPES.2022.03170.
Improved Control Strategy of Soft Open Points for Distribution Network with High Penetration of Distributed Generation
摘要
Abstract
Soft open point (SOP) is a new type of power electronic device for power flow regulation in distribution networks. With increasing distributed generation (DG) penetration
a stable but flexible power regulation ability of SOP is particularly important. However
superposition of disturbances and uncertain factors may reduce control performance. Therefore
to enhance anti-disturbance ability and dynamic performance of SOP and improve robustness to internal uncertainties
a control strategy based on improved linear active disturbance rejection control (LADRC) of DC voltage outer loop and fast terminal sliding mode (FTSM) control of inner loop is proposed. Among them
the estimation error and the known part of the total disturbance are added to a linear extended state observer (LESO)
and an improved LADRC method is proposed and applied to constant DC voltage outer loop. Then
by combining dynamic characteristic equation of AC current of SOP
FTSM surface and exponential approach equation
FTSM is applied to inner loop of the SOP to improve response speed and robustness of system. Finally
a simulation model of a three-port SOP connected to a distribution network is built
and effectiveness of the proposed method is verified.