Hongyi Chen, Tianling Shi, Qinghui Huang, 等. Impedance-Based Islanding Detection for DC Microgrid with Multiple Distributed Generators[J]. 中国电机工程学会电力与能源系统学报(英文), 2025,11(5):1997-2011.
Hongyi Chen, Tianling Shi, Qinghui Huang, et al. Impedance-Based Islanding Detection for DC Microgrid with Multiple Distributed Generators[J]. CSEE Journal of Power and Energy Systems, 2025, 11(5): 1997-2011.
Hongyi Chen, Tianling Shi, Qinghui Huang, 等. Impedance-Based Islanding Detection for DC Microgrid with Multiple Distributed Generators[J]. 中国电机工程学会电力与能源系统学报(英文), 2025,11(5):1997-2011.DOI: 10.17775/CSEEJPES.2022.00020.
Hongyi Chen, Tianling Shi, Qinghui Huang, et al. Impedance-Based Islanding Detection for DC Microgrid with Multiple Distributed Generators[J]. CSEE Journal of Power and Energy Systems, 2025, 11(5): 1997-2011.DOI: 10.17775/CSEEJPES.2022.00020.
Impedance-Based Islanding Detection for DC Microgrid with Multiple Distributed Generators
This paper proposes an active islanding method based on impedance measurement for DC microgrids with multiple distributed generators (DGs). In the various presented methods
impedance-based islanding detection faces challenges in DC microgrids with multiple DGs due to the randomness of renewable energy. In the proposed method
the virtual impedance controls are designed to reshape the output impedance of DGs and the input impedance of loads at the detection frequency to ensure a clear distinction between grid-connected conditions and islanding conditions. Thus
the islanding events can be effectively detected under conditions that lead to a distinct decrease in system impedance. In this way
the accuracy of islanding detection is improved. Moreover
a dynamic allocation of the role algorithm is proposed to organize the orderly disturbance injection of DGs without communication
avoiding disturbance dilution. In addition
the selection principle of the frequency of disturbance current is proposed by studying the sensitivity of the point of common coupling (PCC) voltage to the disturbance. As a result
the negative influence of multiple DGs
loads
and disturbance dilution can be avoided compared to the existing methods. Finally
the effectiveness of the proposed method has been verified by both simulation and experimental results.