Zilong Zeng, Yi Tan, Yijia Cao, 等. Security Constrained Stochastic Unit Commitment Considering Fast Correction Control of Battery Storage and VSC[J]. 中国电机工程学会电力与能源系统学报(英文), 2025,11(5):2036-2047.
Zilong Zeng, Yi Tan, Yijia Cao, et al. Security Constrained Stochastic Unit Commitment Considering Fast Correction Control of Battery Storage and VSC[J]. CSEE Journal of Power and Energy Systems, 2025, 11(5): 2036-2047.
Zilong Zeng, Yi Tan, Yijia Cao, 等. Security Constrained Stochastic Unit Commitment Considering Fast Correction Control of Battery Storage and VSC[J]. 中国电机工程学会电力与能源系统学报(英文), 2025,11(5):2036-2047.DOI: 10.17775/CSEEJPES.2021.08390.
Zilong Zeng, Yi Tan, Yijia Cao, et al. Security Constrained Stochastic Unit Commitment Considering Fast Correction Control of Battery Storage and VSC[J]. CSEE Journal of Power and Energy Systems, 2025, 11(5): 2036-2047.DOI: 10.17775/CSEEJPES.2021.08390.
Security Constrained Stochastic Unit Commitment Considering Fast Correction Control of Battery Storage and VSC
With the development of power electronics-based units such as battery storage systems (BSS) and voltage source converters (VSC) that can quickly respond
the power system will receive a lot of security benefits from these fast control units. To fully utilize fast correction controls from the BSS and grid coupling VSC (GCVSC)
this paper presents a new
$N-1$
security-constrained stochastic unit commitment (SUC) model for hybrid AC and DC grids. In the proposed model
those fast-control units are used to avoid overloading and voltage violations in the post-contingency short-term period. In order to maintain good voltage profiles during pre- and post-contingency periods
the reactive power support ability of the BSS and the GCVSC is also considered. To improve calculation speed
the Bilinear Benders decomposition-based method is used to solve the proposed SUC model. Results on two examples
hybrid AC and DC grids
show that the proposed method can provide highly effective unit commitment solutions with post-contingency corrective actions
especially suitable for avoiding post-contingency short-term security problems in day-ahead dispa