Jun Zhao, Weijiang Chen, Kejie Li, et al. Analysis of Conducted Disturbance via Current Transformer Due to Switch Operation of GIS Disconnector in UHV Substation[J]. CSEE Journal of Power and Energy Systems, 2023, 9(3): 1227-1234.
Jun Zhao, Weijiang Chen, Kejie Li, 等. Analysis of Conducted Disturbance via Current Transformer Due to Switch Operation of GIS Disconnector in UHV Substation[J]. 中国电机工程学会电力与能源系统学报(英文), 2023,9(3):1227-1234.DOI: 10.17775/CSEEJPES.2021.05580.
Jun Zhao, Weijiang Chen, Kejie Li, et al. Analysis of Conducted Disturbance via Current Transformer Due to Switch Operation of GIS Disconnector in UHV Substation[J]. CSEE Journal of Power and Energy Systems, 2023, 9(3): 1227-1234.DOI: 10.17775/CSEEJPES.2021.05580.
Analysis of Conducted Disturbance via Current Transformer Due to Switch Operation of GIS Disconnector in UHV Substation
摘要
Abstract
The characteristics of conducted disturbances via current transformer (CT) caused by switch operations in 1000 kV UHV substations are studied in this paper. Since the broad-band circuit models might have limitations on the stability and accuracy for CT conducted disturbance simulation
a frequency-domain simulation method without circuit synthesis is proposed based on VFTC spectrum and CT transfer characteristics. To improve VFTC simulation accuracy
both the bushing radiation loss and frequency-dependent earth impedance are taken into consideration. Transfer characteristics of three types of windings for the 1000 kV GIS CT are ingeniously measured from a combination of fast and slow impulse tests. Through conducted disturbances simulations in UHV Wuhu substation
bushing radiation loss is found to have a suppression effect on the high-frequency response but the effect of frequency-dependent earth impedance can be ignored. As a result
the maximum amplitude of 84.5 A for the conducted disturbance is obtained
thus a fast damped oscillatory wave immunity test with no lower than Level 4 from IEC standard is suggested to test the anti-interference performance of the secondary equipment in UHV substation.