Direction Protection Based on Time-domain Travelling Wave for Flexible MTDC Grid
Fault direction identification is important for dc protection
which cannot only be used in directional pilot protection
but also plays an important role in non-unit protection (for excluding backward faults). Direction criteria based on <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\Delta i$ and <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\mathrm{d}i/\mathrm{d}t$ have been utilized in LCC-HVDC system extensively. However
the reliability and sensitivity of the protection are significantly influenced by fault transition resistance and line distribution capacitors. In a flexible MTDC grid
boundary characteristics of the DC inductor can be utilized to judge the fault direction. But when the DC inductor is only installed at converter outlet
this kind of direction protection cannot work. Therefore
this paper analyzes the frequency characteristic of the fault traveling wave (TW) first. On this basis
the direction protection based on the time-domain TW is proposed
which is immune from frequency-dependence line parameters. Compared with existing direction protection
it has higher operation reliability and sensitivity
and is independent of the line boundary. Finally
the feasibility and superiority of the designed direction protection are verified by simulation cases based on PSCAD/EMTDC.