Guanyu Tian, Yingzhong Gu, Zhe Yu, 等. Enhanced Denoising Autoencoder-aided Bad Data Filtering for Synchrophasor-based State Estimation[J]. 中国电机工程学会电力与能源系统学报(英文), 2022,8(2):640-651.
Guanyu Tian, Yingzhong Gu, Zhe Yu, et al. Enhanced Denoising Autoencoder-aided Bad Data Filtering for Synchrophasor-based State Estimation[J]. CSEE Journal of Power and Energy Systems, 2022, 8(2): 640-651.
Guanyu Tian, Yingzhong Gu, Zhe Yu, 等. Enhanced Denoising Autoencoder-aided Bad Data Filtering for Synchrophasor-based State Estimation[J]. 中国电机工程学会电力与能源系统学报(英文), 2022,8(2):640-651.DOI: 10.17775/CSEEJPES.2020.06270.
Guanyu Tian, Yingzhong Gu, Zhe Yu, et al. Enhanced Denoising Autoencoder-aided Bad Data Filtering for Synchrophasor-based State Estimation[J]. CSEE Journal of Power and Energy Systems, 2022, 8(2): 640-651.DOI: 10.17775/CSEEJPES.2020.06270.
Enhanced Denoising Autoencoder-aided Bad Data Filtering for Synchrophasor-based State Estimation
摘要
Abstract
Due to its high accuracy and ease of calculation
synchrophasor-based linear state estimation (LSE) has attracted a lot of attention in the last decade and has formed the cornerstone of many wide area monitor system (WAMS) applications. However
an increasing number of data quality concerns have been reported
among which bad data can significantly undermine the performance of LSE and many other WAMS applications it supports. Bad data filtering can be difficult in practice due to a variety of issues such as limited processing time
non-uniform and changing patterns
and etc. To pre-process phasor measurement unit (PMU) measurements for LSE
we propose an improved denoising autoencoder (DA)-aided bad data filtering strategy in this paper. Bad data is first identified by the classifier module of the proposed DA and then recovered by the autoencoder module. Two characteristics distinguish the proposed methodology: 1) The approach is lightweight and can be implemented at individual PMU level to achieve maximum parallelism and high efficiency
making it suited for real-time processing; 2) the system not only identifies bad data but also recovers it
especially for critical measurements. We use numerical experiments employing both simulated and real-world phasor data to validate and illustrate the effectiveness of the proposed method.