Zhiyun Han, Qingmin Li, Yujin Guo, 等. Influence of Repetitive Impulse Waveforms on Surface Discharge Characteristics and Insulation Life for Polyimide Film[J]. 中国电机工程学会电力与能源系统学报(英文), 2024,10(2):746-755.
Zhiyun Han, Qingmin Li, Yujin Guo, et al. Influence of Repetitive Impulse Waveforms on Surface Discharge Characteristics and Insulation Life for Polyimide Film[J]. CSEE Journal of Power and Energy Systems, 2024, 10(2): 746-755.
Zhiyun Han, Qingmin Li, Yujin Guo, 等. Influence of Repetitive Impulse Waveforms on Surface Discharge Characteristics and Insulation Life for Polyimide Film[J]. 中国电机工程学会电力与能源系统学报(英文), 2024,10(2):746-755.DOI: 10.17775/CSEEJPES.2020.05530.
Zhiyun Han, Qingmin Li, Yujin Guo, et al. Influence of Repetitive Impulse Waveforms on Surface Discharge Characteristics and Insulation Life for Polyimide Film[J]. CSEE Journal of Power and Energy Systems, 2024, 10(2): 746-755.DOI: 10.17775/CSEEJPES.2020.05530.
Influence of Repetitive Impulse Waveforms on Surface Discharge Characteristics and Insulation Life for Polyimide Film
摘要
Abstract
Accelerated insulation aging problems under high frequency repetitive impulses in power electronic transformers are drawing more and more attention in modern power systems. Partial discharge (PD) characteristics including discharge inception voltage
phase distribution and statistical characteristics on polyimide (PI) surface under different impulse waveforms and the insulation life of PI films are studied in this paper. We carry out experiments based on PD and insulation lifetime test systems
using five different types of repetitive impulses
including three bipolar waves and two unipolar waves. The experimental results show that there is little variation in discharge inception voltage under different waveforms
but great variation in phase distribution and statistical characteristics of PD. In addition
insulation life is approximately the same under different waveforms with the same polarity
and the aging rate under bipolar waveforms is larger than that under unipolar waveforms. We explain the differences between the bipolar and unipolar waveforms on insulation life
which can be concluded that the surface charge under unipolar waveform accumulates more significnatly compared with bipolar waveform and decreases the electric filed strength in discharging the air gap and inhibits surface discharge from occurring.
Discharge Characteristics of Bubbles at Interface Between AlN Ceramic and FC-72 Liquid
Understanding DC Partial Discharge: Recent Progress, Challenges, and Outlooks
Evolutionary Characteristics of Interfacial Defects Inside Vehicle-Mounted High-Voltage Cable Termination for High-Speed Trains
Frequency Selective Metamaterial Based on Surface Discharge Behavior of the CSRR Skin Under Lightning Strike
Effect of Interface Charge on Partial Discharge Characteristics of Oil-Pressboard Insulation in Non-Uniform AC/DC Combined Electric Field Under Different Temperatures
相关作者
Shenyang Mo
Xuebao Li
Zhibin Zhao
Xiang Cui
Chuanyang Li
Tohid Shahsavarian
Mohamadreza Arab Baferani
Kerry Davis
相关机构
Electrical and Computer Engineering, University of Connecticut, Storrs