Ge Cao, Guannan Lou, Wei Gu, 等. $H_{\infty}$ Robustness for Distributed Control in Autonomous Microgrids Considering Cyber Disturbances[J]. 中国电机工程学会电力与能源系统学报(英文), 2024,10(2):696-706. DOI: 10.17775/CSEEJPES.2020.04110.
Ge Cao, Guannan Lou, Wei Gu, et al. $H_{\infty}$ Robustness for Distributed Control in Autonomous Microgrids Considering Cyber Disturbances[J]. CSEE Journal of Power and Energy Systems, 2024, 10(2): 696-706. DOI: 10.17775/CSEEJPES.2020.04110.
Ge Cao, Guannan Lou, Wei Gu, 等. $H_{\infty}$ Robustness for Distributed Control in Autonomous Microgrids Considering Cyber Disturbances[J]. 中国电机工程学会电力与能源系统学报(英文), 2024,10(2):696-706. DOI: 10.17775/CSEEJPES.2020.04110.DOI:
Ge Cao, Guannan Lou, Wei Gu, et al. $H_{\infty}$ Robustness for Distributed Control in Autonomous Microgrids Considering Cyber Disturbances[J]. CSEE Journal of Power and Energy Systems, 2024, 10(2): 696-706. DOI: 10.17775/CSEEJPES.2020.04110.DOI:
$H_{\infty}$ Robustness for Distributed Control in Autonomous Microgrids Considering Cyber Disturbances
The physical connections and logical relationships between microgrids and communication networks allow microgrids to develop into typical cyber-physical systems (CPSs). With the extensive use of open communication mechanisms
the impact of cyber disturbances in public communication networks cannot be diminshed. In this paper
a parameter optimal method for a distributed secondary controller based on the robust control theory and consensus algorithm is presented to enhance the robustness of a secondary control system under data disturbance
parameter perturbation
and time delay. First
a distributed secondary control strategy of microgrids is demonstrated that coordinates frequency and voltage restoration and power sharing. Then
considering the impact of cyber events on the secondary control
a distributed robust controller gain design method is proposed to satisfy the
$\boldsymbol{H}_{\infty}$
performance index. The solution of the distributed robust control is transformed into a linear matrix in equation problem and latency margin is simultaneously obtained. Finally
a test microgrid CPS is simulated with and without time de
lay to investigate the impact of cyber events on system operational states and the effectiveness and robustness of the proposed method.