Fault Location Detection of Transmission Lines in Noise Environments Based on Random Matrix Theory
Regular Papers|更新时间:2026-10-15
|
Fault Location Detection of Transmission Lines in Noise Environments Based on Random Matrix Theory
Fault Location Detection of Transmission Lines in Noise Environments Based on Random Matrix Theory
中国电机工程学会电力与能源系统学报(英文)2022年8卷第4期 页码:1233-1241
作者机构:
Key Laboratory of Modern Power System Simulation and Control & Renewable Energy Technology, Ministry of Education (Northeast Electric Power University),Jilin,China
Jun An, Zihan Deng, Haipeng Chen, 等. Fault Location Detection of Transmission Lines in Noise Environments Based on Random Matrix Theory[J]. 中国电机工程学会电力与能源系统学报(英文), 2022,8(4):1233-1241.
Jun An, Zihan Deng, Haipeng Chen, et al. Fault Location Detection of Transmission Lines in Noise Environments Based on Random Matrix Theory[J]. CSEE Journal of Power and Energy Systems, 2022, 8(4): 1233-1241.
Jun An, Zihan Deng, Haipeng Chen, 等. Fault Location Detection of Transmission Lines in Noise Environments Based on Random Matrix Theory[J]. 中国电机工程学会电力与能源系统学报(英文), 2022,8(4):1233-1241.DOI: 10.17775/CSEEJPES.2020.04090.
Jun An, Zihan Deng, Haipeng Chen, et al. Fault Location Detection of Transmission Lines in Noise Environments Based on Random Matrix Theory[J]. CSEE Journal of Power and Energy Systems, 2022, 8(4): 1233-1241.DOI: 10.17775/CSEEJPES.2020.04090.
Fault Location Detection of Transmission Lines in Noise Environments Based on Random Matrix Theory
摘要
Abstract
Fault detection and location are critically significant applications of a supervisory control system in a smart grid. The methods
based on random matrix theory (RMT)
have been practiced using measurements to detect short circuit faults occurring on transmission lines. However
the diagnostic accuracy is influenced by the noise signal in the measurements. The relationship between mean eigenvalue of a random matrix and noise is detected in this paper
and the defects of the Mean Spectral Radius (MSR)
as an indicator to detect faults
are theoretically determined
along with a novel indicator of the shifting degree of maximum eigenvalue and its threshold. By comparing the indicator and the threshold
the occurrence of a fault can be assessed. Finally
an augmented matrix is constructed to locate the fault area. The proposed method can effectively achieve fault detection via the RMT without any influence of noise
and also does not depend on system models. The experiment results are based on the IEEE 39-bus system. Also
actual provincial grid data is applied to validate the effectiveness of the proposed method.