Effect of Multiple Models of Closed-Loop Transfer Functions on Inter-Harmonic Oscillation Characteristics of Grid-Connected PMSG
Regular Papers|更新时间:2026-10-15
|
Effect of Multiple Models of Closed-Loop Transfer Functions on Inter-Harmonic Oscillation Characteristics of Grid-Connected PMSG
Effect of Multiple Models of Closed-Loop Transfer Functions on Inter-Harmonic Oscillation Characteristics of Grid-Connected PMSG
中国电机工程学会电力与能源系统学报(英文)2024年10卷第5期 页码:1955-1964
作者机构:
1. Key Laboratory of Far-shore Wind Power Technology of Zhejiang Province, Huadong Engineering Corporation Limited, Power China,Hangzhou,China
2. Dept. of Electrical Engineering, State Key Lab of Control and Simulation of Power Systems and Generation Equipment, Tsinghua University,Beijing,China
Jingyi Li, Jianjun Yang, Xiaorong Xie, 等. Effect of Multiple Models of Closed-Loop Transfer Functions on Inter-Harmonic Oscillation Characteristics of Grid-Connected PMSG[J]. 中国电机工程学会电力与能源系统学报(英文), 2024,10(5):1955-1964.
Jingyi Li, Jianjun Yang, Xiaorong Xie, et al. Effect of Multiple Models of Closed-Loop Transfer Functions on Inter-Harmonic Oscillation Characteristics of Grid-Connected PMSG[J]. CSEE Journal of Power and Energy Systems, 2024, 10(5): 1955-1964.
Jingyi Li, Jianjun Yang, Xiaorong Xie, 等. Effect of Multiple Models of Closed-Loop Transfer Functions on Inter-Harmonic Oscillation Characteristics of Grid-Connected PMSG[J]. 中国电机工程学会电力与能源系统学报(英文), 2024,10(5):1955-1964.DOI: 10.17775/CSEEJPES.2020.03920.
Jingyi Li, Jianjun Yang, Xiaorong Xie, et al. Effect of Multiple Models of Closed-Loop Transfer Functions on Inter-Harmonic Oscillation Characteristics of Grid-Connected PMSG[J]. CSEE Journal of Power and Energy Systems, 2024, 10(5): 1955-1964.DOI: 10.17775/CSEEJPES.2020.03920.
Effect of Multiple Models of Closed-Loop Transfer Functions on Inter-Harmonic Oscillation Characteristics of Grid-Connected PMSG
Establishing a suitable closed-loop transfer function model for the grid-connected PMSG system is the key basis in performing inter-harmonic characteristics analysis. Multiple closed-loop transfer functions can be constructed when different components of the converter controller are taken into account. However
the effect of different components of the converter controller on inter-harmonic stability analysis is not clear. In this paper
the complete transfer function
considering different loops
is first given. Based on the complete closed-loop transfer function
the DC-link
PLL and voltage forward-feed are removed step by step to derive different closed-loop transfer functions. The inter-harmonic related poles of different closed-loop transfer functions are further calculated to analyze the effect of closed-loop transfer functions on inter-harmonic characteristics analysis. Finally
by performing time domain simulation
the correctness of the theoretical analysis results is verified. The results show that under the conditions of a weak AC system
each loop of the converter control system will reduce the stability of the inter-harmonic in the sub-synchronous frequency range and influence the inter-harmonic oscillation frequency. The transfer function needs to consider the influence of each loop to accurately calculate the inter-harmonic stability of the system.
Stability Analysis for Direct-drive Wind Farm Transmitted via Flexible DC System Based on Dynamic Energy
Operating-Point Identification from Dimensions of Alternating Signal Based on Incremental Iterative Mapping Mechanism for Analyzing Dynamics of AC Systems
Non-unit Fault Location for MMC-HVDC Grids Based on Geometric Features of Fault Voltage
Analysis and Suppression of Oscillation of Weak Grid-tied VSC Using RLC Circuit Model