Pilot Protection Based on Amplitude Comparison for Renewable Power Teed Lines
Fault behaviors of inverter-interfaced renewable energy generators (IIREGs) are quite diverse from those of synchronous generators (SGs). They show the variable system impedance
the limited current and low inertia
so the proportional brake differential protection installed on the transmission line has a high risk of failure for phase-phase failures. To cope with this adaptive problem
a new pilot protection is proposed considering the huge differences in both current amplitudes. Also
an improved criterion is presented for a scenario with a teed line. The existing protection principles focus excessively on the fault current characteristics of IIREGs
so they cannot operate correctly once IIREGs do not output their fault current. This happens when IIREGs produce no power or the circuit breakers exactly reclose on permanent failures. However
the proposed method has good performance for the above cases. The proposed method only requires current amplitude information
and in this case the strict synchronizing measurement is not necessary. Case studies are performed under different fault conditions
and they confirm the proposed method has good performance under different fault conditions. Furthermore