Jun Yi, Wei Hu, Zijie Zhang, 等. Steady-state voltage reactive compensation method for half-wavelength transmission lines considering equivalent power supply impedance[J]. 中国电机工程学会电力与能源系统学报(英文), 2020,6(4):841-847.
Jun Yi, Wei Hu, Zijie Zhang, et al. Steady-state voltage reactive compensation method for half-wavelength transmission lines considering equivalent power supply impedance[J]. CSEE Journal of Power and Energy Systems, 2020, 6(4): 841-847.
Jun Yi, Wei Hu, Zijie Zhang, 等. Steady-state voltage reactive compensation method for half-wavelength transmission lines considering equivalent power supply impedance[J]. 中国电机工程学会电力与能源系统学报(英文), 2020,6(4):841-847. DOI: 10.17775/CSEEJPES.2018.00390.
Jun Yi, Wei Hu, Zijie Zhang, et al. Steady-state voltage reactive compensation method for half-wavelength transmission lines considering equivalent power supply impedance[J]. CSEE Journal of Power and Energy Systems, 2020, 6(4): 841-847. DOI: 10.17775/CSEEJPES.2018.00390.
Steady-state voltage reactive compensation method for half-wavelength transmission lines considering equivalent power supply impedance
Half-wavelength AC transmission (HWACT) refers to transmission along lines with an electrical distance of half the power frequency wavelength. The voltage amplitude at the sending terminal is equal to that at the receiving terminal in steady-state. Furthermore
the voltage at the receiving terminal does not vary with load. However
the electrical distance has been extended in actual HWACT lines because of the impact of the equivalent power supply impedance
so the attractive characteristics no longer hold. As a result
reactive power compensation methods with constant power factor and constant voltage are needed and these are presented in this paper. The steady-state operational characteristics
the calculation methods of additional reactive power compensation and the admittance of a controllable shunt reactor are also given. The methods proposed in this paper are relatively simple to implement
and the calculations involved are straightforward
resulting in effective voltage stabilization. The results indicate that such compensation methods can increase the transmission capacity while maintaining a relatively low voltage along the line.