Yishi Yue, Hengxin He, Weijiang Chen, 等. Characteristics of long air gap discharge current subjected to switching impulse[J]. 中国电机工程学会电力与能源系统学报(英文), 2015,1(3):49-58.
Yishi Yue, Hengxin He, Weijiang Chen, et al. Characteristics of long air gap discharge current subjected to switching impulse[J]. CSEE Journal of Power and Energy Systems, 2015, 1(3): 49-58.
Yishi Yue, Hengxin He, Weijiang Chen, 等. Characteristics of long air gap discharge current subjected to switching impulse[J]. 中国电机工程学会电力与能源系统学报(英文), 2015,1(3):49-58. DOI: 10.17775/CSEEJPES.2015.00035.
Yishi Yue, Hengxin He, Weijiang Chen, et al. Characteristics of long air gap discharge current subjected to switching impulse[J]. CSEE Journal of Power and Energy Systems, 2015, 1(3): 49-58. DOI: 10.17775/CSEEJPES.2015.00035.
Characteristics of long air gap discharge current subjected to switching impulse
摘要
Abstract
Measuring the pre-breakdown current of long sparks in air is important for investigating the discharge mechanism. Since the breakdown of long air gaps is conducted by a series of streamer-leader processes
the corresponding current signals cover a bandwidth of 0 to more than 20 MHz. Measurement accuracy of the current from the high voltage side is affected by the displacement current and impulse electromagnetic interference. In this paper
a coaxial current sensor with a DC bandwidth of 74.45 MHz is developed. A displacement current-restrained electrode structure is proposed to reduce the equivalent capacitance between the current sensor and the ground over 30 times. Combined with the digital optical fiber synchronous acquisition unit
a current measurement system for long air gap discharge is established. For the purpose of the UHV system's external insulation optimization design
the discharge current waveform of a 6 m rod-plane air gap under positive switching impulse voltage with 250 μs and 1000 μs time to crest is obtained. Discharge images and stressed voltage are combined to analyze the continuous feature of a current waveform under critical time to crest impulse and discontinuous feature under long front duration impulse. For the purposes of a lightning protection study
the current waveform of a 10 m rod-plane air gap is subjected to negative switching impulse. Finally
the pulse characteristics of the current corresponding to the single channel and branching stepped negative leader are discussed.