YIN Xun-qiang, YUAN Wen-zhi, WANG Gui-xuan. Static-dynamic coupling analysis of pumping station of nuclear power plant under complicated heterogeneous site condition[J]. 2016, 37(S2): 745-752.
YIN Xun-qiang, YUAN Wen-zhi, WANG Gui-xuan. Static-dynamic coupling analysis of pumping station of nuclear power plant under complicated heterogeneous site condition[J]. 2016, 37(S2): 745-752.DOI: 10.16285/j.rsm.2016.S2.094.
EPR nuclear power plant circulation water pump house(HPX) which is the seismic 1 item supplies water for circulating cooling water (CRF) system. So the influence of heterogeneity is particularly important in the site foundation. Based on the actual conditions of a domestic nuclear power plant site
a three dimensional finite element model of the pump house foundation is established by ANSYS platform. And the mechanical properties and spatial distribution pattern of xenoliths are simulated in detail. The static and dynamic time history analysis method is proposed based on Newmark method. This method can be used to comprehensively evaluate the vertical deformation of the foundation
bearing capacity
the base of the bottom surface rate
anti-sliding and anti-overturning stability
etc. The results of analysis show that
in the distribution of the site under practical
the existence of xenoliths has a little influence on the safety of pumping house foundation. Part compressive stress out of specification has no influence on overall stability. The foundation does not need to be processed because the index of the evaluation can meet the requirements of the specification. At the same time
the calculated results also verify reliability and good engineering applicability of the Static-Dynamic coupling analysis model. The model has the potential to solve the nonlinear dynamic problem of the complex nuclear power structure
with the combination of the ANSYS which has rich unit model and the capacity of nonlinear analysis.