钟选斌, 伍绍君, 牛勇, et al. Cause Analysis and Treatment of Chemical Accidents in Commissioning of Large Thermal Power Units[J]. 2021, (3): 118-122. DOI: 10.16056/j.2096-7705.2021.03.024.
the medium pressure of sub-system also changes from low pressure to medium and high pressure
which improves the requirements of debugging and operation. Chemical accidents and anomalies occurred in commissioning of large thermal power units
such as leakage of high-speed mixed bed
low pH value of stator cooling water
water vaporization spewing out directly from artificial sampling tray
turbidity of water clarifying tank of water purification station
pH value of slurry of receiving tower dropping to strong acid
etc. Analysis of its causes are mainly water cap quality
water cap installation quality and other unqualified. Unreasonable resin proportion and selection. Water vapor samples are not cooled in time in the circulating pump; Unreasonable dosage of water purification station
too much water intake load adjustment. Absorption tower wrong slurry supply way
etc. The treatment measures are to check the water cap winding wire and water cap installation gap. Reasonable selection of resin. Timely adjustment of sampling parts of the sampling door
pressure reducing valve. Control the dosage of water purification station
equipment load. Adjust the absorption tower slurry supply mode
etc. The treatment of these accidents is very representative and can provide reference experience for debugging and operation workers when dealing with similar chemical accidents.