韩欣月, 王力, 赵书龙, et al. Analysis of Line-to-ground Short-circuit Accident for 35 kV Single-core Cable[J]. 2021, (2): 88-92. DOI: 10.16056/j.2096-7705.2021.02.017.
35 kV单芯电缆线路接地短路事故分析
摘要
35 kV单芯电缆线路在运行过程中
金属屏蔽层会产生感应电势。当电缆两端接地
会发生接地环流现象
接地环流过大会破坏绝缘性能
极易发生电缆单相接地短路。结合国内某风电场35 kV单芯电缆线路接地短路事故案例
采取现场详勘和实验室检测相结合的手段
分析事故主要原因是电缆金属屏蔽层质量未达到国家质量标准要求
事故诱因为施工工艺不规范
留下质量隐患
对暴露的问题提出更换同批次不合格电缆
立即整改不规范施工工艺、加强电缆线路的日常运行维护管理等具体解决措施。
Abstract
During the operation of 35 kV single-core cable line
the metal shielding layer will produce induced electromotive force. If both ends of the cable are grounded
it will create a grounding circular current. Excessive grounding circulation will destroy the insulation performance of cable and easily cause cable single-phase grounding short circuit. Based on the case of grounding short circuit accident of 35 kV single-core cable in a domestic wind power plant
the main cause of the accident is that the cable metal shielding layer did not meet the national quality standard by means of field survey and laboratory test. The other cause of the accident is that the construction technology is not standard
leaving hidden quality trouble. For the exposed problems
it is proposed to replace the unqualified cables in the same batch
immediately rectify the non-standard construction technology
and strengthen the daily operation and maintenance management of the cable line.