Dissolvedoxygen is the most important cause to the oxidation corrosion
which is one of the important factors to the safety operation and lifetime of circulating water piping. One new kind of thermal deoxygenation system of heat-supply network make-up water suitable for low-temperature heating reactoris proposed. By adding preheater
deaerator
electric heater and related control valves
the thermal deoxygenation of the heat-supply network make-up water is realized
the main parameters of the hot heat-supply network and deaerator equipment and the deaerator electric power of the 200 MW low temperature heating reactor are determined
and the selection calculation of the main equipments in the system is given for reference.